Page  2

Power  supply  .....................................................................................  230/240  VAC  50/60  Hz  +/-  10%
Power  consumption  ......................................................................................................................3,1  W
Range of relay contact  switching  free of voltage ............................................................. 10A  250V resistive
Insulation  ...........................................................................................................................  Class  II
Types  of  gas  detected  ................................................................................. Natural Gas - for  Natural  gas
                                                                                                                                            LPG- for LPG model
Detection  sensor  .......................................................................................................................  Catalytic
Alarm  sensitivity    .........................................................................................................  At  10%  of  L.E.L.
Precision  of  the  detector  .............................................................................................................  1%  FS
Sensor’s faults  detected by  Fault Circuit  ................................................... Interruption,  short circuit,  or wear
Test  Phase  Duration  .............................................................................................................  60  seconds
Audible and visual signal alarm by ............................................................. LED diode and buzzer 85 dB at 1 m
Selection  of relay  working mode  ........................................................................................  through  Jumper
Test  buttons  ...........................................................................................................................      built-in
Command  electrovalve  ................................................................................................  class  A    o  classe  B
Functioning  Temperature  ...............................................................................................    -10°C  to  +40°C
Functioning  Humidity .........................................................................................  0÷90%  RH not  condensed
Degree  of  protection  ......................................................................................................................  IP42
Dimensions    .......................................................................................................................  115x150x50

CHECK the integrity of the probe after having removed it from the box.
Check  that  the  data  written  on  the  box  correspond  to  the  type  of  gas  used.
When  doing  the  electrical  connections,  follow  the  drawing  closely.
Any  use  of  the  detector  for  purposes  other  than  the  intended  one  is  considered  improper,  and  as  a  result  of
which  BEINAT  S.r.l.    therefore  disclaims  any  responsibility  for  possible  damages  caused  to  people,  animals
or  objects.
INSTALLATION
When  performing  the  installation,  please  remind  that  if  you  pierce  the  GS911K  container,  it  will  lose  its
properties  and  its  conformity  to  REGULATIONS.
TERMS  and  EXPECTATIONS:  The  installation  of  the  GS911K  detector,  its  ordinary  and  extraordinary
maintenance,  and  its  out  of  service  removal  at  the  end  of  the  functional  life  guaranteed  by  the  manufacturer,
must  be  carried  out  by  authorized  and/or  specialized  personnel.
Do  not  allow  it  to  become  wet.
The  detector  can  be  seriously  damaged  when  immersed  in  water.
Do  not  drop  it.
Heavy  knocks  or  falls  during  transportation  or  installation  can  damage  the  appliance.
Avoid  abrupt  temperature  fluctuations.
Sudden  temperature  variations  can  cause  condensation  and  the  probe  could  work  poorly.
Cleaning
Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.
Absolutely  avoid  using  any  cloth  dipped  in  thinners,  alcohol  and  chemical  detergents.

Precautions

Technical    Specifications

Functional Features Of Gas Sensors
The  installation  of  the  GS911K  detector,  its  ordinary  and  extraordinary  maintenance,  and  its  out  of  service
removal  at  the  end  of  the  functional  life  guaranteed  by  the  manufacturer,  must  be  carried  out  by  authorized
and/or  specialized  personnel.
The  CATALYTIC  technology  sensor  duration  is  guaranteed  for  6  years  (in  clean  air).
The  detector’s  functioning  temperature  ranges  from  -10°C  to  +  40°C.

WARNING!

The  CATALYTIC  probe  does  not  tolerate  a  gas  detection  exceeding  100%  of  L.E.L.,  with  consequent  natural
death  of  the  sensor.
Each  immediate  puff  of  gas  that  exceeds  100%  of  L.E.L.  takes  away  months  of  life  from  the  sensor.
The  detector  must  be  tested  by  simulating  the  presence  of  gas  by  issuing  it  from  a  pre-calibrated  testing
aerosol.
A  common  cigarette  lighter  near  the  sensor  does  not  guarantee  excellent  functioning.

MAINTENANCE

The  user  periodically  (every  6  months)  must  perform  a  check  of  the  operation  of  the  control  unit  by

spraying  a  suitable  test  gas  at  the  base  of  the  probes  connected  until  the  alarm  condition  is  reached.

•  At  least  once  a  year  make  a  more  accurate  check  by  a  specialist  technician.

•  Disabling  the  detector  must  be  carried  out  by  qualified  personnel.

Содержание Beinat GS911K

Страница 1: ...0 VAC The elegance and the prestige that have always made BEINAT S r l stand out from its competitors together with the concept of home fitness comes the household gas detector GS911K detects through...

Страница 2: ...ed and or specialized personnel Do not allow it to become wet The detector can be seriously damaged when immersed in water Do not drop it Heavy knocks or falls during transportation or installation ca...

Страница 3: ...closing the two poles the relay will work at pulse in the sense that once tripped the alarm relay will close the C and NA contacts for about 90 seconds and then will reopen them This is needed to pre...

Страница 4: ...ing switch appropriately identified as the detector sectioning device must be incorporated in the electrical system suitably located and easily accessible ATTENTION The relay is voltage free 1 2 3 4 5...

Страница 5: ...2 3 4 5 LV LG LR Rel ay Buzzer Wiring 1 2 3 4 5 LV LG LR Rel ay Buzzer Wiring Elettrovalvola NC 1 2 3 4 5 LV LG LR Rel ay Buzzer Wiring 1 2 3 4 5 LV LG LR Rel ay Buzzer Wiring 1 2 3 4 5 LV LG LR Rel a...

Страница 6: ...should not be installed in environments where the temperature drops below 10 C or rises above 40 C The detector is equipped to detect different types of gases and according to these its must to be po...

Страница 7: ...ses the connected equipment Check that connections are correct and that the jumper which leads to the common voltage of the relay has been carried out all the relays are voltage free Check the scheme...

Страница 8: ...sible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or it...

Отзывы: