DCU20
User Manual rev. 19
Page 26/29
Name
Short name
Value
ALARM_INPUT_OVERLOAD_END
IOLE
The
maximum
input
current
reached during the alarm.
Description
The measured input current returns below the alarm threshold.
Name
Short name
Value
ALARM_OUTPUT_OVERLOAD_START
OOLS
Threshold current triggering the
alarm.
Description
The measured output current exceeds the alarm threshold. The alarm threshold is set to 22A.
Name
Short name
Value
ALARM_OUTPUT_OVERLOAD_END
OOLE
The maximum output current
reached during the alarm.
Description
The measured output current returns below the alarm threshold.
Name
Short name
Value
ALARM_BATTERY_UNDERVOLT_START
BUVS
Threshold voltage triggering the
alarm.
Description
The measured battery voltage is lower than the alarm threshold. The threshold is 80% of the battery
deep discharge voltage (§5.2.7).
Name
Short name
Value
ALARM_BATTERY_UNDERVOLT_END
BUVE
The minimum battery voltage
reached during the alarm.
Description
The measured battery voltage returns above the alarm threshold.
Name
Short name
Value
ALARM_BATTERY_LOW_START
BLOWS
Threshold voltage triggering the
alarm.
Description
During discharge the measured battery voltage is lower than the battery low voltage threshold
(§5.2.8).
Name
Short name
Value
ALARM_BATTERY_LOW_END
BLOWE
The minimum battery voltage
reached during the alarm.
Description
The measured battery voltage returns above the battery low voltage threshold (§5.2.8).
Name
Short name
Value
ALARM_BATTERY_OVERVOLT_START
BOVS
Threshold voltage triggering the
alarm.
Description
The measured battery voltage exceeds the alarm threshold. The threshold is the battery charge
voltage (§5.2.5) + 10%.
26
DCU20_1680-21539-0006-E-1117