5.2.2

 

Recommendations

 

To  ensure  correct  installation  and  functioning  of  the  Modbus  control  fan,  please  keep  in  mind  following 
recommendations:

 

1- 

Please strip the wire 5cm as a maximum as shown below:

  

 

2

-  Communication  cables  cannot  be  wound.  If  it  were  done,  they  could  act  as  an  antenna.  Communication 

cables that are not used have to be cut and left inside the shielded tube as shown below. 

3

- Please keep always a distance of at least 20cm between the power and the data cable. If both cables must 

cross at some point, please ensure that they do so at a 90º angle to prevent interference. 

 

 

 

 

 

 

 

 

WARNING! 

 
Do not strip the communication cable more than 5cm. 

Failure to do so may lead interferences. 

 
 

Do not wind the unused communications cable. 

Failure to do so may lead interferences.

 

 
 

Maintain a minimum distance between electrical and communications wiring. 

Failure to do so may lead 

interferences.

 

 

 
Avoid power zones. 

Failure to do so may lead interferences. 

 

 

 

DRIVE 
BOX 

Содержание AIRWALL

Страница 1: ...AIRWALL Installation Manual Issued March 2020 ANIM13CI Rev C...

Страница 2: ...ON 24 07 2019 A First Edition 06 09 2019 B Control Box up to 6 ud 16 03 2020 C Update 2020 product Technical documents are regularly updated Anemoi reserves the right to modify the contents of this ma...

Страница 3: ...ECHANICAL INSTALLATION 8 4 1 Wall aperture measurements 9 4 2 Control box installation 10 5 ELECTRICAL INSTALLATION 11 5 1 Box Control 12 5 2 Modbus control optional 12 5 2 1 Multiple Fan Installation...

Страница 4: ...ire or other accidents Ensure that the wires are held securely and protected from abrasion chaffing overload or other damage Risk of serious or fatal electrical shock fire or other accidents Turn Off...

Страница 5: ...interior to the exterior of buildings This fan is used to increase comfort drawing hot air from inside buildings to the outside allowing air renewal and extraction of stale indoor air The AIRWALL fan...

Страница 6: ...pm 450rpm 370rpm Protection degree IP55 IP55 IP55 Sound level 63dBA 68dBA 70dBA Total weight 37kg 62kg 70kg Motor type DC Brushless motor FAN PERFORMANCE Airflow 40 020m3 h 60 300m3 h 62 220m3 h Cover...

Страница 7: ...are listed in the following table Model WIDTH mm DEPTH mm HEIGHT mm WEIGHT kg AIRWALL 100 1065 400 1065 AIRWALL 120 1380 400 1380 AIRWALL 150 1530 400 1530 3 2 Packing list The following tables inclu...

Страница 8: ...made to install the fan The wall and frame must be sufficiently supportive to support the weight of the fan and fix it properly to avoid overturning The Anemoi AIRWALL fan is designed so that slats a...

Страница 9: ...electrical shock 4 1 Wall aperture measurements The frame and pre frame measurements to be carried out for the correct assembly of the AIRWALL are established These measures already include 1cm of se...

Страница 10: ...ed to the wall For these purposes the box has four holes in the corners The measurements of the box and perforations are detailed below CAUTION Install the control box in a safe area Failure to do so...

Страница 11: ...cable cross sections and ambient temperature Copper 60 C 75 C conductors are recommended To ensure the fan operation the control box must be connected to the fan and the power supply The distance betw...

Страница 12: ...s connexion please see the Modbus Configuration Parameters document provided by Anemoi The external control is connected direcly to the fan board using shielded cable type modbus RS485 2x2x0 50 mm POS...

Страница 13: ...roller is connected to the different by using control connections A B and GND The following figure shows the detail of the control connectors WARNING The earth meshes of each cable section must remain...

Страница 14: ...ube as shown below 3 Please keep always a distance of at least 20cm between the power and the data cable If both cables must cross at some point please ensure that they do so at a 90 angle to prevent...

Страница 15: ...e data display as shown in table 3 Adjust the potentiometer to the required speed 4 Check the speed in the VFD screen To stop the fan perform the procedure in reverse NO DATA DISPLAY CONTENT Normal ti...

Страница 16: ...Operating panel 7 2 The data display NO DISPLAY NAME FUNCTION 1 S 10 Gear numerical Display the gear value 2 M 0 Timing time Show how long the fan is turned off 3 OK STOP E IPM AUTO Start Stop Fail S...

Страница 17: ...82V Check power connections E UV Voltage below level Check input voltage more than 85V Check power connections E IPM Fail connexion Check the connections of wires Check power cable Rd ER E XT Communic...

Страница 18: ...sure that the fan does not make any noises or vibrations Check that the blades have not received any impact Yearly Check that there no alarms or faults in the variable speed drive located in the contr...