AIRPOLE
17
5
ELECTRICAL INSTALLATION
WARNING!
Follow the instructions and recommendations contained in this section.
Failure to do so may result in
serious injury or death.
The Anemoi AIRPOLE motor is controlled by a variable frequency drive installed in the control box. The control
VFD is already factory configured to obtain the correct motor performance. To ensure the fan operation, the
installers must connect the VFD to the power supply and to the motor.
Before installing the VFD, it is necessary to remove power supply to prevent any accident. Check that power supply
is disconnected before starting the installation.
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Copper (60°C/75°C) conductors are recommended.
Follow any national or local regulation regarding electrical installations.
WARNING!
Follow national and local electrical regulations.
Failure to do so may result in serious injury or death.
Check that power supply is disconnected before starting the installation.
Failure to do so may result in
serious injury or death.
Do NOT install the fan with wet hands.
Failure to do so may result in serious injury or death.
Do not change the VFD configuration.
Otherwise, the warranty would be voided
.
The Anemoi AIRPOLE engine must be connected to the power supply with an electrical voltage of 230V (I, 50/60Hz)
through the control VFD. The control box includes a terminal box to allow for smooth connection to the power
supply.
You may use shielded or unshielded cables. The maximum cable length between the control box and the engine
should be 100m for unshielded and 50m for shielded cables. Please root the cables along the floor using the
shortest possible path.
Electrical and control wiring should be installed in separated circuits to prevent interference.
WARNING!
Do NOT use wires with worn or damaged insulation.
Doing so may result in serious or fatal electrical shock,
fire or other accidents.
Ensure that the wires are held securely and protected from abrasion, chaffing, overload or other
damage
. Risk of serious or fatal electrical shock, fire or other accidents.
Do NOT connect the motor to the input line directly.
Failure to do so may result in equipment damage.