Page 22
UNSCREW RETAINERS
AND OPEN PANEL
REMOVE FILTER
LIFT AND REMOVE
AIR FILTER
PAC22AX
UNSCREW RETAINERS AND
OPEN PANEL, REMOVE FILTER
PAC15AX/ET15AX
FIG 4
8) ROUTINE MAINTENANCE
The air filter must be kept clean, never al-
low to become choked with dust or dirt. If
allowed to do so, the performance of the
unit will become impaired, resulting in loss
of air flow, freezing up of the evaporator coil
and possible component damage.
ACCESSING THE FILTER PAC15AX/
ET15AX
Open the lower front panel, filter is located
in front of the evaporator. A second filter is
fitted to the rear panel on of an ET15.
PAC22AX
Lift out the return air grille on the
front face of the unit, Fig 4. On refitting the
filter ensure that it is correctly positioned
covering the whole rear face of the grille.
The filter (see Fig. 4) can be washed in
warm, soapy water, rinsed and shaken dry
before replacement. Frequency of cleaning
depends upon application and can only be
determined by the user. However, you
should never allow more than two months
to elapse between cleaning. The probable
life of the filter will be about one year and
spares are available from the supplier of the
unit itself. Failure to have filter fitted during
operation will cause serious damage.
The refrigeration circuit inside the room unit
is fitted with a HIGH and a LOW pressure
sensing switch. They are both manually
resettable. A pencil or screwdriver with
gentle pressure on the knob behind is all
that is required to re-set.
Necessary access is provided either via the
lower front panel on PAC15AX/ET15AX and
through the control console of the PAC22AX.
HOWEVER, DO NOT ATTEMPT TO RESET
WITHOUT FIRST DISCOVERING WHY
THE TRIP OCCURRED IN THE FIRST
PLACE.