MAXXflo Water Heater
12
12
CONDENSE DRAIN
Condensation is formed in the heater and this must be
continuously discharged into a drain. A trap is supplied
which should be connected into a drain via a tundish or
air break. The condense flow must not be allowed to block
otherwise the heater will fail to work correctly.
An air break is required downstream of the trap
to protect the water heater from blockages and
subsequent damage.
Each 30kW module could produce up to 3 litres of condense
per hour while at full load.
SECONDARY RETURN CIRCULATION PUMP
An additional connection for a secondary circulation is
available in the top of the heater that is located between
the hot flow and cold feed ports. We would recommend that
a non-return valve is fitted in the return line.
If a secondary return circuit is fitted with a secondary
pump, please ensure that the flow-rate or heat loss does
not exceed the heater maximum flow-rate or minimum
load. An excessive flow in the secondary circuit could result
in a temperature mixing effect in the heater storage vessel
resulting in a stored water temperature less than the set
temperature (see table below).
Model Type
CWH30
CWH60
CWH90
CWH120
Maximum
0.9
1.8
2.7
3.6
flow rate m
3
/h
Minimum load
kW
6
12
18
24
Circulation Pump
Secondary
Return Line
Cold Water
Fig 2
SECTION 3 • INSTALLATION
Содержание CWH120/200
Страница 8: ...MAXXflo Water Heater 8 8 INSPECTION HATCH INSPECTION HATCH SECTION 2 TECHNICAL DETAILS ...
Страница 9: ...MAXXflo Water Heater 9 9 TECHNICAL DETAILS SECTION 2 INSPECTION HATCH INSPECTION HATCH ...
Страница 13: ...MAXXflo Water Heater 13 13 INSTALLATION SECTION 3 Fig 3A Typical installation Fig 3B Typical installation ...
Страница 26: ...MAXXflo Water Heater 26 26 CWH90 CWH120 STANDARD FLUE SYSTEM DIMENSIONS SECTION 3 INSTALLATION ...
Страница 28: ...MAXXflo Water Heater 28 28 FLUE SYSTEMS Fig 12 SECTION 3 INSTALLATION ...
Страница 39: ...MAXXflo Water Heater 39 39 PARTS LIST SECTION 8 MAXXflo INTERNAL SPARES ITEMS ...
Страница 41: ...MAXXflo Water Heater 41 41 73 74 71 71 75 72 76 77 PARTS LIST SECTION 8 MAXXflo OLD ISSUE SPARES ITEMS ...