Andover Controls Infinity ACC EMX 151 Скачать руководство пользователя страница 2

Click for EMX Menu 

EMX 151 Installation Guide-2

Caution

Be sure you disconnect the Infinet controller’s AC power 
source before you connect any modules.

1.Look at the bottom panel of your Infinet controller. On 

that panel is an expansion port in approximately the 
center of the panel.

2.Look at the EMX 151 module. Notice that it has a 

connector on the top and on the bottom. Plug the top 
connector into the Infinet controller.

3.If you are connecting more than one EMX 151 module 

to your Infinet controller, connect the second one to the 
bottom of the first.

4.Set the BOARD switch to 1 on the first EMX 151 on the 

controller, and the BOARD switch to 2 on the second 
EMX 151.  If you do not plan to connect more than one 
EMX 151, you should set the BOARD switch to 1.

Never set two modules of the same model number to the 
same board number.

3. Connect the External Power Supply 
(if necessary)

If you are installing multiple modules, you may need an 
external power supply. To determine what you need, refer 
to the ACC EMX Modules Configuration Guide.

Figure 2 shows where you connect the external power supply to 
the 2-pin Berg type connector on the EMX 151.

Figure 2.  Location of External Power Connection 
and Jumper for External Power

EMX151

BOARD

1

2

RET

I
V

OUTPUT

A

RET

I
V

OUTPUT

B

EXTERNAL

POWER

Connect
External
Power 
Supply
Here

Power
Supply
Jumper 

4. Reposition Jumper on One Module

The Berg type connector immediately below the external 
power supply connection has a jumper that you reposition 
to indicate you are using external power.

You change the jumper position only on the module or mod-
ules connected to the external power supply, not on any other 
modules.

Note

You need to change the jumper position only on the mod-
ule(s) actually connected to an external power supply. Never 
change the jumper position of other modules.

Figure 3 shows the jumper in the two possible positions, 
one for the internal power supply, the other for the external.

Figure 3.  Jumper Positions for Internal and External 
Power Supplies

Each is set to the internal position when you receive it.

Wire the Outputs

Wire Voltage Outputs

You wire the outputs for voltage as follows:

1.Slip the appropriate wire under the V screw and tighten 

the screw down on it.

Figure 4 illustrates the wiring for voltage outputs.

Figure 4.  Wiring Diagram for Voltage Outputs 

2.Slip the ground wire under the RET screw and tighten 

the screw down on it.

Wire Current Outputs

You wire the outputs for current as follows:

Jumper Position,
External Power
Supply

Jumper Position,
Internal Power
Supply

V

RET

+

RL > or = 4 K

Technical Manuals Online! - http://www.tech-man.com