Andover Controls Infinity ACC EMX 151 Скачать руководство пользователя страница 1

Copyright © 1992 Andover Controls Corporation, 300 Brickstone Square, Andover, MA 01810  All Rights Reserved.

Click for EMX Menu 

Your warranty is effective for 18 months starting on the 
date the system is shipped.

Before You Begin

You can connect one or more EMX modules to most Infinet 
controllers that have an expansion port. The particular con-
trollers are covered in the ACC EMX Modules Configuration 
Guide
 (also enclosed with this product).The configuration 
guide also tells how many inputs and outputs are allowed for 
any a particular controller. Before you proceed, be sure the 
controller allows modules and the number and type of mod-
ules you plan to use. 

Warning

Be sure wiring and installations comply with local, state, 
and national electrical codes.

Figure 1 shows the EMX 151 module.

Figure 1.  The EMX 151 Module

Dimensions

Each EMX 151 module is approximately 6.13 

×

 4.88

 ×

 1.52 in.

Power Requirements

The first module receives power from the controller and 
operates on 24 VDC +/–15%/–5%. You can add addition-

EMX151

BOARD

1

2

RET

I
V

OUTPUT

A

RET

I
V

OUTPUT

B

EXTERNAL

POWER

al EMX modules other than an EMX 151 if you have an 
external power supply source of 24 VDC and properly 
connect the modules to it. See the ACC EMX Modules 
Configuration Guide
 for more information.

The EMX 151 consumes up to 70 mA at 24 VDC.

Environmental Requirements

The EMX 151 operates in the same environment that any 
Infinet controller operates in.

Output Characteristics

You can wire the outputs as either voltage or current. The 
voltage output has 2.5 mA maximum output over the 
range of 0 to 10 VDC. The input impedance of the device 
being controlled can be no less than 4000 

.

Resolution of each voltage output is 2.44 mV.

The current output has a 0 to 20 mA control signal.  The 
input impedance of the device being controlled can be no 
greater than 1000 

.

The circuitry that produces the 0 to 20 mA signal acts as a 
“current sourcing device.” It sources the current to ground.

Resolution of each current output is 4.88 

µ

A.

Accuracy of voltage and current is +/–0.1 % of the range 
of the output.

Both outputs are fused at   A.

Install the EMX 151

1. Unpack

Be careful when unpacking the unit or units to not damage 
the packaging material—you must reuse it if you ship the 
product back for repair.

2. Connect to the Infinet Controller

Connect the module to the Infinet controller as outlined in 
the steps that follow.

1
8

---

ACC EMX 151
Installation Guide

Order No. 30-3001-278

Version 1.2

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Отзывы: