Andover Controls CMX 220 Скачать руководство пользователя страница 1

Andover Controls Corporation

i

TOC

CMX 220
Installation Guide

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание CMX 220

Страница 1: ...Andover Controls Corporation i TOC CMX 220 Installation Guide Technical Manuals Online http www tech man com firealarmresources com...

Страница 2: ...Massachusetts 01810 All Rights Reserved Published by the Engineering Department at Andover Controls Corporation IMPORTANT NOTICE This product is subject to change without notice This document does not...

Страница 3: ...controllers on an EnergyNet network It first presents site preparation information and then step by step installation instructions We recommend you read EnergyNet and Infinet Configuration Guide to pl...

Страница 4: ...iv CMX 220 Installation Guide Technical Manuals Online http www tech man com firealarmresources com...

Страница 5: ...tning Protection 6 Building Ground Requirements 7 Inspecting the Ground 8 Environmental Requirements 8 Laying Out the Site Setup 8 Installing the CMX Controller 10 Unpacking 10 Parts Required 10 Mount...

Страница 6: ...ker 17 Powering Up the CMX 18 Connecting the Battery 19 Interpreting Status Lights Inside Cabinet 20 Using the CLEAR MEMORY Button 21 Connecting the Andover Controls Service Tool 21 Appendix RS 232 Po...

Страница 7: ...wer Supply Wire 12 Figure 3 Cable Ports and Connectors on the CMX 220 Controller 15 Figure 4 Infinet Cable Wiring 16 Figure 5 Audio Speaker Wiring 17 Figure 6 System Activity Status Lights 20 Figure A...

Страница 8: ...viii CMX 220 Installation Guide Tables Table 1 Number of Infinet Controllers Allowed on Various Models of CMX 6 Technical Manuals Online http www tech man com firealarmresources com...

Страница 9: ...t controllers Every CMX controller has a 2 pin speaker connec tion where you can connect an audio speaker for use with your modem You can also connect to a terminal or printer over a modem from the CM...

Страница 10: ...enerates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions in this manual may cause harmful interference to radio communications Operation o...

Страница 11: ...e or the operation of your equipment the telephone company will give you notice in writing to allow you to make any changes necessary to main tain uninterrupted service If you have any questions about...

Страница 12: ...he problem and informed of your right to file a complaint with the FCC In the event repairs are ever needed on the Infinity CMX controller they should be performed by Andover Controls Corporation or a...

Страница 13: ...orm Infinet are 24 gauge single twisted pair tinned shielded copper wire Use the following cables1 or their equivalents Note You must use shielded cables for Infinet to ensure compliance with the Clas...

Страница 14: ...e Lightning Protection Warning When running cables Infinet or input output wire between buildings you must install lightning arresters for Infinet to prevent electromagnetic disturbances Use lightning...

Страница 15: ...l grounds An example of a substandard ground is a galvanized steel cold water pipe As the pipe corrodes it does not act as a true ground The corro sion acts as an insulator raising the potential of th...

Страница 16: ...ondensing The controller must be in an Underwriter Laboratories approved enclosure Laying Out the Site Setup You may want to draw a map of where you plan to put each controller and store it in a noteb...

Страница 17: ...nity CX controller on the same Infinet with a CMX controller Find the tag attached to each controller that gives the number of the con troller Before you remove any tags be sure the tag has all of the...

Страница 18: ...see the appendix for specifications Mounting and Wiring Caution You must encase the CMX in a UL approved cabinet to keep its Open Class rating STILL NOT APPROVED Figure 1 shows the back and sides of t...

Страница 19: ...5 200 10 400 11 50 8 75 45 4 Places 1 59 9 72 03 10 54 05 55 23 REF 2 000 015 R 117 Full RAD 4 Places R 20 4 PLCS 0 281 003 000 Hole Thru Install PEM Self Clinching Standoff BSO 8632 24 CI or Equivale...

Страница 20: ...all three wires GND RET and 24V Otherwise the controller could malfunction 2 Notice that the three wires at the end of your AC cable are black white and green 3 Place the green wire under the metal p...

Страница 21: ...ot connect to an LBUS or Infinet cable and cannot connect to a modem You may connect a printer to it but since it is the only port and a terminal is required in most situations a terminal be longs the...

Страница 22: ...n emulation package such as CROSSTALK to the CMX controller as follows 1 Set up the terminal or computer on a table within cable s length of the controller 2 Open the front of your controller cabinet...

Страница 23: ...roller Connecting to the Built in Modem If your CMX has a built in modem you connect a telephone line to the modem as follows 1 Open your cabinet door and look for the MODEM label The telephone jack i...

Страница 24: ...o the CMX using the following procedure 1 Open the front of the controller cabinet Notice that to the lower left is a port labeled Infinet Notice that the end of the Infinet cable has two wires and a...

Страница 25: ...th a minus sign middle and tighten the screw down on them 5 Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD bottom and tighten the screw down on them Connec...

Страница 26: ...controller To start the controller turn on the AC power source or close the power connection and the controller starts automatically The real time clock is always running on battery power independent...

Страница 27: ...ing the Battery Once you have closed the AC power connection you connect the bat tery The battery 3 5 V lithium battery is to the right and below the transformer the yellow box in the upper left corne...

Страница 28: ...ower comes up The lights blink to indicate activity The purposes of the five lights are as follows CPU Flashes every 0 2 sec that the controller is active RD Flashes every 0 5 sec when the modem is re...

Страница 29: ...is the red button in the lower center of controller You press the red button only to cold start the controller Connecting the Andover Controls Service Tool The SERVICE PORT on the far left side of th...

Страница 30: ...22 Infinity CMX Installation Guide Technical Manuals Online http www tech man com firealarmresources com...

Страница 31: ...on cable for connect ing a modem to either a controller or a terminal However to connect any terminal to a controller you should use a cable with the required pinouts Figure A 1 shows the required and...

Страница 32: ...onnector to Terminal 1 To and from are in relation to the Infinity CMX controller Pin Number Purpose Direction RTS Chassis TD RD CTS GND V V Required From From To To From From YES NO YES YES YES YES N...

Страница 33: ...End 2 3 7 2 3 7 or IBM PS 2 25 pin Connecting to VT 100 Connecting to Infinity CMX Female End Female End 2 3 5 2 3 IBM AT 9 pin Connecting to Connecting to Infinity CMX 7 2 3 7 2 3 7 Female End Femal...

Страница 34: ...A 4 Infinity CMX Installation Guide Technical Manuals Online http www tech man com firealarmresources com...

Страница 35: ...e Underwriter Laboratories requirements 8 10 ERROR light inside 21 F features unique to CMX 1 G ground correcting 8 inspecting 8 requirements 7 I Infinet connecting 16 lightning arrester for 6 Infinet...

Страница 36: ...e of 21 shields for Infinet cable connecting 17 speaker amplification 5 T TD light inside 20 temperatures for operating 8 terminal connecting 14 U Underwriter Laboratories enclosure requirements 8 10...

Страница 37: ...30 3001 203 Infinity CMX 220 Installation Guide Rev D Technical Manuals Online http www tech man com firealarmresources com...