Copyright © 1992 Andover Controls Corporation, 300 Brickstone Square, Andover, MA 01810  All Rights Reserved.

Click for EMX Menu 

Your warranty is effective for 18 months starting on the 
date the system is shipped.

Before You Begin

You can connect one or more EMX modules to most Infinet 
controllers that have an expansion port. The particular con-
trollers are covered in the ACC EMX Modules Configuration 
Guide
 (also enclosed with this product).The configuration 
guide also tells how many inputs and outputs are allowed for 
any  particular controller. Before you proceed, be sure the 
controller allows modules and the number and type of mod-
ules you plan to use. 

Warning

Be sure wiring and installations comply with local, state, 
and national electrical codes.

Figure 1 shows the EMX 156 module.

Figure 1.  The EMX 156 Module

Dimensions

Each EMX 156 module is approximately 3.75 

×

 

4.25 ×

1.5 in.

EMX156

BOARD

OUTPUT

A

OVERRIDE

A

B

OUTPUT

B

LOAD

A

LOAD

B

DATE

1

2

U

L

INPUTS

VOLTS 24V

AMPS

36MA

OUTPUTS

VOLTS 240V

AMPS 3.5A

LISTED

ACCESSORY EQUIPMENT

58B2

FOR USE WITH

SCX

LCX AND TCX UNITS

,

24VDC
CLASS

I I

AUTO OFF ON AUTO OFF ON

R

Power Requirements

The EMX 156 consumes up to 32 mA at 24 VDC.

For power requirements when installing multiple modules 
see the ACC EMX Modules Configuration Guide.

Environmental Requirements

The EMX 156 operates in the same environment that any 
Infinet controller operates in.

Output Characteristics

The two outputs are Form A (SPST) AC outputs with 
override and feed back detection.

All outputs may be programmed or set with manual over-
ride switches.

The Form A outputs are rated for 3 A at 24–280 VAC.

Install the EMX 156

1. Unpack

Be careful when unpacking the unit or units to not damage 
the packaging material—you must reuse it if you ship the 
product back for repair.

2. Connect to the Infinet Controller

Connect the module to the Infinet controller as follows:

Caution

Be sure you disconnect the Infinet controller’s AC power 
source before you connect any modules.

1.Look at the bottom panel of your Infinet controller. On 

that panel is an expansion port in approximately the 
center of the panel.

2.Look at the EMX 156 module. Notice that it has a 

connector on the top and on the bottom. Plug the top 
connector into the Infinet controller.

ACC EMX 156
Installation Guide

Order No. 30-3001-349

Version 1.3

www.PDF-Zoo.com