5

Dry Contact Relay

 

 
To use your dry contact output fail relay you must connect a 9-pin D connector to the unit.  You must 
use pins one and six as is indicated on page 6 in the remote connector diagram. 
 

The relay is factory preset to fail in the closed position when the low output LED and buzzer 
come on.  If you wish to have the relay fail in the open position when the low output LED and 
buzzer come on, you must take the cover off the unit and move the jumper to the other 
position on J7.  J7 is located next to the relay. 

 
 
 

 
 
 

To change the position of the jumper, first turn the unit off and disconnect the unit from both the 

power and batteries.  Next, turn the unit on for 30 seconds to discharge the capacitors, then turn it off 

again.  Turn the unit upside down and remove the four screws.  Remove the cover and locate J7.  It 

will be next to the relay as is shown in the above diagram.  Simply move the jumper to the desired 

position as is shown in the above diagram.  Replace the cover and re-install the four screws.  

Reconnect the unit to the power and batteries.

Содержание VTC310 Series

Страница 1: ...VTC310 Series Voltage Converter Installation Operation Manual...

Страница 2: ...provided if it will not fit outlet have proper cord installed by a qualified electrician Improper connection can result in a risk of an electric shock WARNING Do not use as a battery charger Only mode...

Страница 3: ...ut Fuse MDA 6 MDA 3 MDA 2 Output Voltages Nominal op 12 24 32 Actual Vdc 13 6 0 05 27 2 0 05 36 3 0 05 Output Crowbar 16 0 0 5 V 32 0 1 0 V 42 7 2 0 V Output Amps cont 20 10 7 5 Output Amps max 25 13...

Страница 4: ...OPTION The units may be configured for load sharing if they are equipped with the optional output isolation diodes To confirm that your unit has these diodes use an ohmmeter to measure the resistance...

Страница 5: ...he unit should sound the buzzer to alert you prior to shutting itself down You should immediately check the indicators to determine the cause of the shutdown LOW OUTPUT Indicates that the output volta...

Страница 6: ...r off the unit and move the jumper to the other position on J7 J7 is located next to the relay To change the position of the jumper first turn the unit off and disconnect the unit from both the power...

Страница 7: ...L A remote control panel may be connected to the voltage converter using a 9 pin D connector that attaches to the side of the voltage converter The remote control panel and D connector are part of the...

Страница 8: ...remedy the defect after having a reasonable number of opportunities to do so 5 Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone else shall render t...

Отзывы: