The purpose of the Equalize Option is to deliberately overcharge the battery at a low rate of 

current to ensure that all cells are fully charged and to reduce the chance of sulfation. During 

the Equalize cycle, the cells, which are fully charged, will produce Hydrogen gas, and the cells, 

which are undercharged, will be brought up to full charge. An Equalize cycle should be done 

once every 2-3 months, or whenever battery capacity appears to be diminished. The Equalize 

Option also includes a battery temperature sensor to compensate the charging voltage 

for battery temperature, as well as to shut the charger down if the battery should become 

overheated. A 2nd temperature sensor can be added to allow monitoring of both batteries if 

the charger is connected to 2 banks of batteries. 

An Equalize cycle can be initiated at any time by simply pressing the equalize start button 

located in the hole labeled EQ SEL. This button is deliberately recessed to prevent accidental 

operation. It is most easily pressed by using a ballpoint pen. If the charger is in the middle 

of charging the battery (the Charging LED is on), the Equalize LED will flash. Once the main 

charging cycle is complete, the Equalize cycle will begin and the Equalize LED will stay on all 

the time. If the Charging LED is off when the button is pressed, the Equalize cycle will begin 

immediately. 

Remote Control Option

Equalize Option

A remote control panel may be connected to the inverter using a 9-pin D-connector, which 

attaches to the battery charger. The remote control panel and D connector are part of the 

remote control option. The remote control panel allows the unit to be operated remotely as 

well as duplicating all the diagnostic indicators and audible alarm

REMOTE CONNECTOR

This connector is located on the side of the unit. Important: To prevent the possibility of High 

Voltage Electrical Shock, do not power up the battery charger unless all wiring from the unit to 

the remote is securely connected. Do not remove the dust cover from the DB-9 connector if the 

remote is not being used.

IMPORTANT: This remote is to be used 

only on Battery Chargers manufactured 

by Analytic Systems.

Содержание BCD310 Series

Страница 1: ...S DC Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers I...

Страница 2: ...Copyright 2005 2016 Analytic Systems Ware 1993 Ltd Revised May 19 2016...

Страница 3: ...G RISK OF EXPLOSIVE GASES i WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT E...

Страница 4: ...erfill For a battery without cell caps carefully follow manufacturer s recharging instructions 3 BATTERY CHARGER LOCATION i Never place battery charger directly above battery gases from battery will c...

Страница 5: ...otection and output overvoltage crowbar Optional features include a high quality digital volt ammeter factory install only and remote panel monitoring with On Off control Specifications Input Voltages...

Страница 6: ...en the output and case Therefore the unit may be mounted on any surface without fear of electrolysis or ground fault Designed and manufactured by ANALYTIC SYSTEMS WARE 1993 LTD 8128 River Way Delta BC...

Страница 7: ...able for the correct sizing of the circuit breaker in the distribution panel A ground stud is provided to bond the chassis to local ground to reduce or eliminate EMI To ensure spark free connections t...

Страница 8: ...harge the batteries at maximum current and the charging light will be on After a period of time which may be minutes to hours the batteries will reach the absorption voltage 3 stage or float voltage 2...

Страница 9: ...charges the battery at a constant current until the battery voltage reaches a slightly elevated level The battery is maintained at this voltage while the charging current diminishes to a low value and...

Страница 10: ...e short circuit condition returns Turn the unit off disconnect the faulty load and reconnect it only after the fault is found and rectified If the condition still exists even after all the loads have...

Страница 11: ...the other position on J11 J11 is located next to the relay To change the position of the jumper first turn the unit off and disconnect the unit from both the power and batteries Next turn the unit on...

Страница 12: ...tion It is most easily pressed by using a ballpoint pen If the charger is in the middle of charging the battery the Charging LED is on the Equalize LED will flash Once the main charging cycle is compl...

Страница 13: ...ed on a platform made of wood Prior to placing the batteries on the wooden platform a cavity is hollowed out such that the sensor will fit inside the cavity and be flush with the surface Place the sen...

Страница 14: ...14 Page intentionally left blank...

Страница 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed o...

Страница 16: ...Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage...

Отзывы: