Dry Contact Relay

To use your dry contact output fail relay you must connect a 9-pin D connector to the unit. You 

must use pins one and six as is indicated on page 7 in the remote connector diagram.

The relay is factory preset to fail in the closed position when the low output LED and buzzer 

come on. If you wish to have the relay fail in the open position when the low output LED and 

buzzer come on, you must take the cover off the unit and move the jumper to the other position 

on J11. J11 is located next to the relay.

To change the position of the jumper, first turn the unit off and disconnect the unit from both 

the power and batteries. Next, turn the unit on for 30 seconds to discharge the capacitors, and 

then turn it off again. Remove the six screws holding on the cover, turn the unit upside down, 

remove the cover and locate J11. It will be next to the relay as is shown in the above diagram. 

Simply move the jumper to the desired position as is shown in the above diagram. Replace the 

cover and re-install the four screws. Reconnect the unit to the power and batteries.

Содержание BCD305 Series

Страница 1: ...S DC Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers I...

Страница 2: ...Copyright 2005 2016 Analytic Systems Ware 1993 Ltd Revised May 19 2016...

Страница 3: ...VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN...

Страница 4: ...caps carefully follow manufacturer s recharging instructions 3 BATTERY CHARGER LOCATION i Never place battery charger directly above battery gases from battery will corrode and damage converter ii Nev...

Страница 5: ...indicators for low input voltage low output voltage and over temperature Safety features include reverse input protection over temperature shutdown current limiting short circuit protection with autom...

Страница 6: ...CD305 12 24 Input Volts DC 10 5 14 10 5 28 Input Amps max 30 30 Output Volts DC 13 6 0 5 V 27 2 0 5 V Charging Amps 26 13 Output Crowbar Output Volts x 1 3 1 Input Fuses AGC 20 x 2 Output Fuse AGC 30...

Страница 7: ...wires as follows Red to Positive Black to Negative POWER CONNECTION Two positive output terminals and two negative output terminals are provided Connect only one wire to each terminal Note that the c...

Страница 8: ...minals Operation Troubleshooting If the load exceeds the continuous rating for too long a period the internal temperature sensor will cause the unit to stop boosting the input voltage until the unit h...

Страница 9: ...it and move the jumper to the other position on J11 J11 is located next to the relay To change the position of the jumper first turn the unit off and disconnect the unit from both the power and batter...

Страница 10: ...otely as well as duplicating all the diagnostic indicators and audible alarm REMOTE CONNECTOR This connector is located on the side of the unit Important To prevent the possibility of High Voltage Ele...

Страница 11: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed o...

Страница 12: ...Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage...

Отзывы: