Installation
Allow at least 1 inch of clearance all around the case for cooling. The best mounting configu-
ration is to mount the unit on a vertical surface oriented as shown. Use #10 screws of the
appropriate type for the mounting surface to securely mount the unit.
There is 1500 volts of isolation between the input and output, and the input and case. There
is 500 volts (1500V for 48V output units) of isolation between the output and case. Therefore,
the unit may be mounted on any surface without fear of electrolysis or ground fault.
The unit is supplied with a 5 foot power cable. This should normally be adequate to connect to
a source of power. If you must extend the power cable be sure to use a 3 conductor grounded
type extension cable. For hard wiring to a source of power, cut off the plug, and strip the wires
as necessary. The wire colors are
All connections should be made inside an appropriate junction box. The maximum current
draw from the 110 VAC supply is 5.2 amps, so a 7 amp circuit breaker should be used in the
circuit panel. For a 220 VAC supply, 2.6 amps is the maximum current draw, so a 4 amp circuit
breaker should be used in the circuit panel to feed power to the BCA 310.
To reduce radio noise to the absolute minimum, it may be necessary to bond the case to
ground. To do this, remove one the screws that mount the output terminal strip to the chassis.
Then place a #6 ring terminal with a ground wire crimped to it under the screw head, and
replace the screw.
Designed and manufactured by:
ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way
Delta, BC V4G 1K5 Canada
p. 604.946.9981 f. 604.946.9983
tf. 800.668.3884 US/Canada
www.analyticsystems.com
[email protected] Revised July 2014
INPUT
FUSE
TO
REMOTE
OUTPUT TERMINAL
ON/OFF
INPUT POWER
OUTPUT
FUSE
110 VAC
220 VAC
Brown - AC Hot
Brown - AC Hot / Phase 1
Blue - AC Neutral
Blue - AC Neutral / Phase 2
Green - Ground
Green/Yellow - Ground