ADE9000 Technical Reference Manual
UG-1098
Rev. 0 | Page 49 of 86
Table 28. Service Type and VCONSEL, ICONSEL Setting Summary
Service Type
Ground
Reference Figure for Reference
Number of
Voltage Sensors
Required
VCONSEL[2:0]
Number of
Current Sensors
Required
ICONSEL
4-Wire Wye
Neutral
3
000
3
0
4-Wire Wye
Isolated
3
000
3
0
3-Wire Delta
Phase B
with Phase B tied to
neutral
2
001;
VB = VA − VC
2
0: IB has current sensor
1: IB = IA − IC
3-Wire Delta
Isolated
Phase B tied to
neutral
2
001;
VB = VA − VC
2
0: IB has current sensor
1: IB = −IA − IC
3-Wire Delta
Isolated
2
100;
VA = VA − VB;
VB = VA − VC;
VC = VC − VB
2
0: IB has current sensor
1: IB = −IA − IC
4-Wire Delta
Neutral
Figure 62 (note that
VA and VB phasor
diagram follows
Figure 58)
3
000
3
0
4-Wire Wye,
Non-Blondel
Compliant
Neutral
2
010;
VB = −VA − VC
3
0
4-Wire Delta,
Non-Blondel
Compliant
Neutral
2
011;
VB = −VA
2
0: IB has current sensor
1: IB = −IA − IC
3-Wire 1PH
Neutral
Not applicable
1 to 2
000
1 to 2
0
3-Wire
Network
Neutral
Not applicable
2
000
2
0
Multiple 1PH
Circuits
Neutral
Not applicable
3
000
3
0