Pre-Installation
6
AXC-TEMP Temperature Control Card and RTS1 Room Temperature Sensor
RTS1 Calibration
To calibrate the RTS1:
1.
Place a reference thermometer near RTS1 unit 1.
2.
Allow the reference thermometer to stabilize for approximately 1-minute.
3.
Adjust calibration POT R1 (CHAN 1) clockwise or counter-clockwise to match the reference
thermometer temperature.
4.
Touch the sensor at bottom of RTS1 unit 1 for 2-seconds to force a temperature change.
5.
Wait approximately 5 seconds for the temperature to stabilize. Then, recheck the display panel
temperature display. Allow the reference thermometer to stabilize approximately one minute,
then check.
6.
If necessary, repeat steps 1 - 5 for RTS1 units 2 - 4, and move the reference thermometer near
each sensor you are calibrating.
FIG. 7
RTS1 to Axcess Cardframe connections
Input White
Green
Drain
Ground Black
Power Red
Input White
Green
Drain
Ground Black
Power Red
Input White
Green
Drain
Ground Black
Power Red
Input White
Green
Drain
Ground Black
Power Red
Green
Drain
Black Ground
Red Power
White Output
Green
Drain
Black Ground
Red Power
White Output
Green
Drain
Black Ground
Red Power
White Output
Green
Drain
Black Ground
Red Power
White Output
Belden 8723,
or equivalent
(Twisted Pair)
Belden 8723,
or equivalent
(Twisted Pair)
Belden 8723,
or equivalent
(Twisted Pair)
Belden 8723,
or equivalent
(Twisted Pair)
RTS1 Unit 1
RTS1 Unit 2
RTS1 Unit 3
RTS1 Unit 4
AXC-TEMP
Axcess
CardFrame
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
When connecting wiring, ensure the Drain and Green wires are used. The
capacitance/filtering effects of these wires are required for accurate measurements.