Wiring and Device Connections
43
Enova DVX-315xHD & DVX-215xHD All-in-One Presentation Switchers - Instruction Manual
FIG. 53 provides the pinouts and signals for the LAN connector and cable.
FIG. 53
RJ-45 Wiring Diagram
FIG. 54 describes the blink activity for the LAN connector and cable.
FIG. 54
LAN Connector / LEDs
AxLink Port and LED (4-pin captive-wire)
The AxLink port (FIG. 55) allows the DVX to support AMX AxLink devices.
FIG. 55 displays the AxLink port and LED.
FIG. 55
AxLink Port and LED
The (green) AxLink LED indicates AxLink data activity:
Off
- No power, or the controller is not functioning properly.
1 blink per second
- Normal operation.
3 blinks per second
- AxLink bus error. Check all AxLink bus connections.
The AxLink port can be used to supply power to downstream AxLink-compatible devices as long as the maximum current draw is
less than 1 Amp. To isolate the DVX from high inrush current, AxLink devices, or potential power faults on the AxLink bus, it is
strongly recommended that you power external AxLink devices from an independent power supply.
NOTE:
The AxLink port provides only limited power to connected AxLink devices. It is recommended to use an alternate power source
when connecting AxLink devices to the DVX.
When using the DVX with the NXA-PDU-1508-8 power distribution unit, do NOT c12V power from any of the NXA-PDU's
AxLink ports to the AxLink power pin.
Refer to the following table for the wiring length information used with the DVX:
Wiring Guidelines
Wire size
Maximum wiring length
18 AWG
154.83 feet (47.19 meters)
20 AWG
98.30 feet (29.96 meters)
22 AWG
63.40 feet (19.32 meters)
24 AWG
38.68 feet (11.79 meters)
A
L
L/A - Activity LED (green)
lights when receiving or
transmitting LAN
data packets
SPD - Link LED (amber) lights when
the LAN cables are connected
and terminated correctly.