Pre-Installation

1. Visually inspect THERM-X-TROL

®

 for any damage. If 

damage exists return product for replacement.

2. Adjust pre-charge to equal incoming pressure.
 

If increasing the pre-charge 

pressure above 55 psig, the 

following steps must be followed:

  a. Tank must be connected to the system with isolation 

valve open.

  b. System must be pressurized to 55-60 psi or slightly 

higher than the pre-charge setting of the tank.

  c. Isolation valve then needs to be closed.
 d. The pre-charge pressure of the tank can now 

be increased to the recommended high pressure 

setting.

  e. Bring system up to pressure, and then open the 

isolation valve to the tank.

 

Failure to follow these instructions could result in 

damage to the bladder or diaphragm and void all 

warranties.

3. Replace and tighten plastic cap on air fitting.
  For commercial water heater installations, contact 

AMTROL for information.

Installation

1.  Install the THERM-X-TROL

®

 on the city supply line to 

the water heater at a point between the water heater 

and backflow preventer, check valve or pressure 

reducing valve (see Figure 1).

2.  Once the THERM-X-TROL

®

 is installed, check the city 

supply line for any leakage. Make repairs if necessary.

3.  Before the initial firing of the water heater, open 

any hot water fixture and draw water until all air is 

removed from the system. Turn the water heater 

temperature control to desired ending temperature 

level, (see water heater instructions).

4.  To relieve initial thermal expansion, slightly open 

a hot water faucet. Continue until water heater 

aquastat temperature is satisfied. Once heater is at 

its operating range, no further bleeding of expanded 

water is required.

5.  

The system water heater and THERM-X-TROL

®

 

will now be operational.  The THERM-X-TROL

®

 will 

control temperature and pressure increases caused 

by thermal expansion to a level well below the water 

heater relief valve setting.

Maintenance

1.  A professional plumber should check the complete 

heating system, including the THERM-X-TROL

®

yearly and more frequently as the system ages.

Operation

1.   The  THERM-X-TROL

®

 is installed in the supply 

line between the backflow preventer and the water 

heater. Its sealed-in air pre-charge prevents water 

from entering it until the system pressure exceeds the 

pre-charge pressure.

2.  

As the water temperature rises, expanded water 

enters the THERM-X-TROL

®

’s non-corrosive water 

reservoir. The pre-charged air chamber absorbs the 

pressure increase, keeping system pressures below 

the relief valve setting.

3.  

As hot water is used, the pressure in the air 

chamber forces water back into the system until the 

THERM-X-TROL

®

 is empty. At this point, the pressure 

in the air chamber once again equals the supply 

pressure.

4.  Water treatment is not to exceed 200° F or fall below 

35° F.

NOTE:

  

Models are listed (ST-5-C thru ST-210V-C) 

under ANSI/NSF Std 61 and City of Los Angeles

.

City Supply

City Supply

B A CK FL O W PREVENTE R 

CHECK  V A L VE OR PRESSUR E 

REDUCING  V A L V E 

W ate r 

Heater 

THERM-X-TROL 

® 
 

S T -5C, S T -12 C 

Relief 

V alv e 

Hot  W ate r 

Hot Water 

THERM-X-TROL

®

ST-20V-C

through ST-210V-C

Water 

Heater 

Figure 1.