![Amtrol PREMIER SERIES Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/amtrol/premier-series/premier-series_application-manual_2937164007.webp)
-7-
With both coils powered, the DC Series models have first-hour ratings up to 637 gallons at a 90°F domestic temperature
rise. See the following charts for sizing:
Commercial Use as Indirect Heater
MBH = BTU output in 1000’s DHW = Domestic Hot Water
APARTMENT SIZING
Model DC-80
PUMP SELECTION
BOILER SELECTION
Units
Heaters
Coil Flow (GPM)
Total for Both Coils
FT/Head
(Use Parallel Plumbing)
MBH Available for DHW
with Maximum # of Units
2-16
1
15
18
400
17-54
2
30
18
800
55-89
3
45
18
1200
90-124
4
60
18
1600
125-160
5
75
18
2000
HOTEL SIZING
Model DC-80
PUMP SELECTION
BOILER SELECTION
Rooms
Heaters
Coil Flow (GPM)
Total for Both Coils
FT/Head
(Use Parallel Plumbing)
MBH Available for DHW
with Maximum # of Units
2-19
1
15
18
400
20-65
2
30
18
800
66-108
3
45
18
1200
109-155
4
60
18
1600
156-200
5
75
18
2000
APARTMENT SIZING
Model DC-120
PUMP SELECTION
BOILER SELECTION
Units
Heaters
Coil Flow (GPM)
Total for Both Coils
FT/Head
(Use Parallel Plumbing)
MBH Available for DHW
with Maximum # of Units
2-21
1
15
18
400
22-82
2
30
18
800
83-138
3
45
18
1200
139-197
4
60
18
1600
198-260
5
75
18
2000
HOTEL SIZING
Model DC-120
PUMP SELECTION
BOILER SELECTION
Rooms
Heaters
Coil Flow (GPM)
Total for Both Coils
FT/Head
(Use Parallel Plumbing)
MBH Available for DHW
with Maximum # of Units
2-24
1
15
18
400
25-95
2
30
18
800
96-162
3
45
18
1200
163-232
4
60
18
1600
233-300
5
75
18
2000