2

AFCI TESTER INSTRUCTIONS

WARNING

Read and understand this material before operating and servicing this
equipment. Failure to understand how to safely operate this tool can result
in accident causing serious injury or death. 

WARNING

Electric shock and fire hazard: Contact with live circuits can result in 
severe injury or death.

WARNING

The Arc Fault Circuit Tester BT-AFT1 is designed  for use on 120 volt wiring systems using
a standard 15 or 20 amp outlet receptacle. Using this product with any other electrical sys-
tem may damage the product or result in injury or death.

1. Plug the unit into an AFCI protected branch circuit outlet. The AC Voltage LED will illumi-
nate, indicating a live circuit. The unit will then perform an internal test, which takes
approximately two seconds.

2. After approximately two seconds, press and hold the Trip button. The Arc LED will flash
during arc simulation, followed by the AC Voltage LED turning off once the AFCI breaker
has tripped.

If the AFCI breaker does not trip, the AC Voltage LED will remain illuminated. The unit is
either plugged into a non-AFCI circuit, the AFCI breaker is defective or there is an error in
the wiring. The unit will not perform a subsequent test until it has been disconnected from
AC voltage and then reconnected.

NOTE: The arc fault circuit breaker tester will automatically reset anytime power is discon-
nected and reconnected for a minimum of one-half second.
All appliances or equipment on the circuit being tested should be unplugged to help avoid
erroneous test.

Not a comprehensive diagnostic instrument but a simple instrument to indicate that the
receptacle is protected by an AFCI.

Содержание BT-AFT1

Страница 1: ...BT AFT1 Arc Fault Breaker Tester Users Manual 99 Washington Street Melrose MA 02176 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us at www TestEquipmentDepot com ...

Страница 2: ...f the factory the instrument has not been tampered with or taken apart Should your instrument fail due to defective materials and or workmanship during this two year period a no charge repair or replacement will be made to the original purchas er Please have your dated bill of sale which must identify the instrument model number and serial number and call the number listed below Repair Department ...

Страница 3: ...m an internal test which takes approximately two seconds 2 After approximately two seconds press and hold the Trip button The Arc LED will flash during arc simulation followed by the AC Voltage LED turning off once the AFCI breaker has tripped If the AFCI breaker does not trip the AC Voltage LED will remain illuminated The unit is either plugged into a non AFCI circuit the AFCI breaker is defectiv...

Страница 4: ...uit consult an electrician If the AFCI does trip reset the AFCI Then insert the AFCI tester into the receptacle to be tested Activate the test button on the AFCI tester for a minimum of 6 seconds when testing the AFCI condition A visible indication on the AFCI tester must cease when tripped If the tester fails to trip the AFCI it suggests a a wiring problem with a totally operable AFCI or b proper...

Отзывы: