25
AC coupled true rms specified from 5 % to 100 % of range
Overload
protection
1000 V dc or 750 V ac rms
AC+DC VOLTS (45Hz to 2kHz)
Ranges
1000 mV, 10 V, 100 V, 750 V
(auto/manual ranging)
Resolution
100 μV
Accuracy
±(1.5 % rdg + 10 dgts) 45 Hz to 500 Hz
±(2.5 % rdg + 10 dgts) 500 Hz to 2k Hz
±(2.5 % rdg + 10 dgts) 45 Hz to 1 kHz
on 750 V range
Crest Factor
≤
3
Input impedance
10 M
Ω
Overload
protection
1000 V dc or 750 V ac rms
DC coupled true rms specified from 5 % to 100 % of range
DC CURRENT
Ranges
100 uA, 1000 μA, 10 mA, 100 mA,
400 mA, 10A (auto/manual ranging)
Resolution
0.1 μA
Accuracy
±(0.5 % rdg + 10 dgts) on 100 uA range
±(0.5 % rdg + 5 dgts)
on 1000 μA to 400 mA ranges
±(1.5 % rdg + 10 dgts) on 10A range
Input impedance
0.5A/1000V fast blow ceramic fuse
6.3×32mm on μA/mA input
10A/1000V fast blow ceramic fuse
10×38mm on 20A input