13
125GMT
Amphenol Network Solutions
All rights reserved. 3.18.20 150566
509.926.6000
— amphenol-ns.com.com
2.2.5 Input Wiring
WARNING! Before connecting input power cables, make sure input power to the panel is turned off.
10. Make sure input power is off before connecti
ng the panel’s input cables to the PDU or battery.
11. For input wiring, crimp dual-hole compression lugs onto #8 AWG to 1/0 AWG copper wires. The choice of
input wiring depends on the following criteria:
•
Input interrupt device rating affects the size of input wiring.
•
Ambient operating temperature affects the type of input wire insulation. For further information,
consult the National Electrical Code (NEC).
12. Insulate the lug barrels with UL94 V-0 rated heat-shrink tubing.
13. Clean terminals and lugs with a non-abrasive, non-metallic pad.
14. If required, lightly coat antioxidant on lugs and input BATT and RTN terminals and then connect lugs to
input terminals, as shown in Fig. 2-5.
15. Tighten nut to
50 in/lb. (5.6 N•m), max.
Fig. 2-5: Input lugs
Содержание 125GMT Series
Страница 1: ...125GMT10 125GMT15 Installation Guide...