MPA3 V6.3 MOTOR PROTECTION RELAY MANUAL
Issue: R0, Date: 11/2010, CRN: 8168
MPAB010 Rev0
MPA3 V6.2 Motor Protection Relay Manual
Page 22
16.3
Ethernet Settings
IP Addr 3
IP Addr 2
IP Addr 1
IP Addr 0
Gateway 3
Gateway 2
Gateway 1
Gateway 0
Subnet Mask
Sets the number of bits (0-32) used to form the Subnet Mask for the device.
16.4
Changing Settings
To change a value of a particular parameter the following steps are required:
a)
Ensure the motor is stopped.
b)
Using the
right
arrow key display the parameter that has to be changed.
c)
Ensure the '
Lock
' input is closed.
d)
Press the
ENT
key. The following warning message will be displayed on the top line of the display
'Change? Ent (ESC)'.
e)
Press the
ENT
key. The top line of the display will change to '
Ent (ESC)'.
f)
Use the
left
and
right
arrows to step through the allowable values until the desired new setting is
displayed. Note that holding the keys in will cause the values to scroll through quickly.
g)
When the desired value is displayed press the
ENT
key. The top line of the display will change to
'Confirm Save:Ent'.
h)
Press the
ENT
key. The top line of the display will change to ' Saving ....’
i)
The top line of the display will change to 'Stored Value'. This completes the setting process.
Review the new value to confirm the correct setting.
j)
Open the lock input.
If the
ESC
key is operated at any stage during the procedure, the modifying sequence is aborted and the setting
reverts to its previously stored value.
These four parameters are combined to create the 32 bit IP address for the device
These four parameters are combined to create the 32 bit default Gateway address for the device