Table 10: Event Log Identifiers and Descriptions
Log Identifier
Description
Power Up
The instant that power is applied to the relay
Pwr Down
Removal of power from the relay
MCR Close
Closure of the Main Contactor Relay
Stopped
Stopping of the outlet by operation of the local stop button
RTU Stop
Stopping of the outlet by operation of the remote stop button
MC Opened
Main Contactor has opened but not initiated by the IPD Relay
MC Fail
Main Contactor Fail Function Trip
CloseFail
Indicates that the MCI Input did not close within 5 seconds of MCR
closing
EC
Trip
Pilot/Earth continuity loop exceeds 45 Ohms
EC Leak T
Leakage resistance between the pilot and earth is less than 1500
Ohms
EL Trip
Earth leakage protection tripped
EFLR Fail
Earth fault lock out test has failed
EL CT Fail
Earth fault current transformer has failed
SC Trip
Trip condition of short circuit protection
OC Trip
Trip condition of over-current or overload protection
RESET
Records resetting of a protection trip function
Setup Mod
Records that set up data has been modified
Fan I Stp
Outlet stopped by fan interlock
uVOLT Trp
Records that voltage was not present on at least one outgoing phase
when the main contactor was closed
MCF F Trp
Internal battery backed main contactor fail trip
RTU ptc T
Operation of the remote termination units PTC
T-mem Rst
Thermal memory has been manually reset to zero
Mem.ERROR
Records that the relay’s non-volatile parameter memory has been
corrupted
- P reset
Internal microprocessor reset
Tmem Loss
The thermal memory data has been corrupted
RTU mem. E
Records that the remote termination unit’s non-volatile memory has
been corrupted or remote termination unit has gone off line while the
outlet is running.
Outlet On
Records RTU machine code and number when main contactor is
closed (proceeded by MCR closed). This log only appears when in
RTU mode.
RTU Off L
Indicates a loss of communications with the RTU.
Meg
Trp
Insulation Test failed
IT: -- . -M
Records the result of the Insulation Test
Insul . Alm
Result of Insulation Test is equal to or less than the alarm level