5.7 Telemetry Test
The telemetry test is intended to allow controlled testing of the system alarms and setpoint flags and the
resultant behaviour of the external interfaces (4-20mA loop and/or Modbus/iMAC) without having to
apply a test gas. This feature can be useful for routine testing and/or commissioning testing.
CAUTION!
The telemetry test may trigger alarms and setpoint flags.
NOTE
Gas values transmitted over Modbus and iMAC have the units of
‘permyriad of full scale’ and may require conversion. Refer to Section
The telemetry test provides several test modes, outlined in Table 8.
Table 8: Telemetry Test Target Values
Test name
Transmitted Gas Value (permyriad
‱
).
See section 6.4.1 for info.
4-20mA output value
UNFORCED
Actual detector gas value (
‱
) OR
fault/warmup value
4mA
– 20mA for normal operation
3/21 mA for actual warmup condition
2/22 mA for actual fault condition
HIGH FAULT
11250
‱
22 mA
HIGH WARMUP 10625
‱
21 mA
100 PERCENT
10000
‱
20 mA
50 PERCENT
5000
‱
12 mA
0 PERCENT
0
‱
4 mA
LOW WARMUP
-625
‱
3 mA
LOW FAULT
-1250
‱
2 mA
Performing a Telemetry Test
1. Access the GG2 maintenance menu via the display UI using the magnetic calibration tool. Refer
to Section 6.1 for an overview of navigating the user interface and the menu structure.
2.
Access the “TELEMETRY TEST” menu. Refer to Figure 15.