5.6.1 Earth Leakage Trip Level
This defines the leakage current which will cause an Earth Leakage trip. The current is detected via the
Earth Leakage CT and is given in RMS. The setting can be any value between 50mA and 5000mA
inclusive. The web server however has used values in set intervals to make adjustment easier and
quicker. These values can be seen below, Table 3.
Table 3: Earth Leakage Trip level
Value
Value
Value
50mA
1100mA
3100mA
100mA
1200mA
3200mA
150mA
1300mA
3300mA
200mA
1400mA
3400mA
250mA
1500mA
3500mA
300mA
1600mA
3600mA
350mA
1700mA
3700mA
400mA
1800mA
3800mA
450mA
1900mA
3900mA
500mA
2000mA
4000mA
550mA
2100mA
4100mA
600mA
2200mA
4200mA
650mA
2300mA
4300mA
700mA
2400mA
4400mA
750mA
2500mA
4500mA
800mA
2600mA
4600mA
850mA
2700mA
4700mA
900mA
2800mA
4800mA
950mA
2900mA
4900mA
1000mA
3000mA
5000mA
5.6.2 Earth Leakage Trip Time
This defines how quickly the Earth Leakage trip will occur when the current through the CT is greater
than the Earth Leakage Trip Level. These values are the maximum trip time, not the minimum (that is a
trip is guaranteed to occur in less than 100ms when set to 100ms). The setting can be any value
between 50ms and 500ms inclusive. The web server however has used values in set intervals to make
adjustment easier and quicker. These values can be seen below.
Table 4: Earth Leakage Trip Time
Max. Trip Time
Max. Trip Time
Instant (50ms)
300ms
100ms
350ms
150ms
400ms
200ms
450ms
250ms
500ms