4.2
Electrical Connections
Once the ECD relay has been mounted at a suitable location, it is necessary to wire it correctly.
Figure
3 shows a typical wiring diagram for the application of the ECD relay. Also refer to drawing ECDM003 for installation
information.
N.O. USER
PUSHBUTTON
RST
PILOT
IS EARTH
IS EARTH
IS EARTH
+
-
D.C. SUPPLY
USER
DEFINED
SAFE AREA
HAZARDOUS
AREA
SAFE AREA
OPTIONAL
STOP
DIODE
1000V, 1A
OPTIONAL
REMOTE
START
RESISTOR
100
Ω
IS EARTH
BAR
MAIN EARTH
BAR
TERMINATION
EARTH BAR
Figure 3: ECD Typical Electrical Application
The table below lists the terminal connections into the ECD relay.
Terminal
Label
Description
1
RST
Reset
2
+
Power Supply Positive
3
-
Power Supply Negative
4
NC1
Relay Output Normally Closed Contact 1
5
NO1
Relay Output Normally Open Contact 1
6
COM1
Relay Output Common Contact 1
7
NO2
Relay Output Normally Open Contact 2
8
COM2
Relay Output Common Contact 2
9
NC
Not connected
10
NC
Not connected
11
NC
Not connected
12
NC
Not connected
13
Pilot
IS Pilot connection (protected by internal IS barrier) (Single core screened,
screen connected to earth at ECD end)
14
IS Earth
IS Earth
15
IS Earth
IS Earth
16
IS Earth
IS Earth
Using a screened cable helps in reducing the induced / coupled voltages. This noise
can cause spurious trips.