Page 76
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
Figure 7-6 13U Cabinet - Top view showing gland plate and cable entry
7.5 Mains termination
The cabinets (13U and 24U) are fitted with a mains isolator and earth stud, located in the top left-hand corner
of the cabinet.
Please ensure the mains is connected – using the appropriately rated cable. The mains cable should conform
to one of the following standards: AS/CA S008, AS/NZS 3191, AS/NZS 5000.1, AS/NZS 3808 or marked with
VW-1.
The circuit breaker in the 24U is rated at 25 amps and 16 amps for the 13U cabinet. Recommended cable for
the 24U is 2.5mm
2
and 1.5mm
2
for the 13U.
Following diagrams show the location of the mains isolator and earth point.
Figure 7-7 13U Cabinet showing the mains isolator, earth point and battery isolator
Содержание EvacU Elite
Страница 1: ...EvacU Elite Emergency Warning Intercom System EWIS Install Commission and User Manual MAN3137 2 ...
Страница 5: ...12 Definitions 121 ...
Страница 78: ...Page 71 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL ...
Страница 80: ...Page 73 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 7 1 24U Cabinet Front and side view ...
Страница 90: ...Page 83 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 2 MIC wiring standard ...
Страница 91: ...Page 84 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 3 MIC wiring voltage reversal ...
Страница 101: ...Page 94 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL 8 7 1 Field wiring Figure 8 6 150Watt amplifier wiring ...
Страница 104: ...Page 97 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL 8 8 3 Field wiring Figure 8 7 Quad radial EIS wiring ...
Страница 107: ...Page 100 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 8 Dual loop EIS wiring ...
Страница 111: ...Page 104 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 10 Network wiring 2 core copper ...
Страница 112: ...Page 105 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 11 Network wiring Single mode single fibre ...
Страница 113: ...Page 106 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 12 Network wiring Single mode dual fibre ...
Страница 114: ...Page 107 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 13 Network wiring Multi mode dual fibre ...
Страница 115: ...Page 108 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 14 Network wiring Mixed Fibre ...
Страница 116: ...Page 109 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 15 Networking wiring Mixed UTP ...
Страница 119: ...Page 112 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 18 Cable routing left hand side ...
Страница 120: ...Page 113 EVACU ELITE INSTALLATION COMMISSIONING AND USER MANUAL Figure 8 19 Cable routing right hand side ...