background image

 

MAN1570-3 

 

 

Description 

The  Apartment  Module  (AM)  is  a  loop  powered  addressable  device  that  helps  reduce  the  costly 
consequences of an unwanted alarm 

An occupant is able to silence a local audible warning, activated by a local smoke detector, and allowing a 
preset time to investigate the cause of the alarm. Local smoke detectors can be connected directly to the AM 
(conventional) or connected to the addressable loop (addressable) and assigned to the AM. 

The local smoke detector is self resetting and if the smoke clears, then the system will return to normal. If 
the smoke remains, then the local audible warning will resound at the expiry of the preset timeout. A local 
smoke detector will NOT cause a general fire alarm. 

The fire system will go into general fire alarm (thus calling the brigade) if: 

 

Any  thermal  detector  has  gone  into  alarm  (conventional  connected  to  the  AM  or  addressable 
connected to the addressable loop) 

 

Any smoke detector in common areas has gone into alarm 

 

Any call point activated 

 
ConfigManager 

is programmed to identify the associations of AM’s with the local smoke detectors 

(conventional and addressable) and adjustment of the “Investigation” period. 

 

AM Features 

 

Loop interface with Short Circuit Isolator (SCI) 

 

On-board Hush Switch with integrated front panel Fire LED (red) and external hush input 

 

Indicators: Poll / SCI LED (green 

 behind cover), Fault LED (yellow 

 behind cover) 

 

100V Line output with EOL monitoring 

 

Conventional Zone circuit with selectable EOL 

 

ADDRESS SWITCH

EOL, EXT HUSH,
POLL SELECTION
SWITCH

POLL LED

FAULT LED

ALARM LED

LOOP IN -VE

LOOP IN +VE

EXTERNAL "HUSH"

ZONE ( CONVENTIONAL DEVICES )

100V LINE

I N

O U T

-
+

-
+

-
+

-
+

-
+

+
+

-
-

100V LINE

TO SPEAKERS

EOL
47K

EOL
22K

4K7

NOTES:
#1 SELECTED EOL MUST BE A APPLIED
EVEN IF THE FUNCTION IS UN-USED

ZONE ( CONVENTIONAL DEVICES ) EOL
10uF ( SW1 / 2 OFF )
6K2   ( SW1 / 2 ON )

FAULT TESTING
1. SHORT/OPEN THE ZONE
2. REMOVE EACH EOL IN TURN
3. REMOVE THE 100V LINE IN

POLL/SCI FAULTS
1. OPEN THE LOOP
2. SHORT THE LOOP

 

Figure 1: Apartment Module general wiring 

Отзывы:

Похожие инструкции для Apartment Module