MAN3069-2 

Page 6 

Ampac Detectors 

 

Cleaning, Maintenance and Functional Test Procedures 

 

Test 

Apparatus 

Smoke 

Detectors 

Series 65, 

Orbis, 

XP95 and 
Discovery 

*See  note 
1

 

Rate of 

rise heat 

detectors 

(Temps 

<90°C) 

*See note 

1

 

High Tem-

perature 

heat detec-

tors 

(fixed/static 

Temps 

>90°C) 

*See note 1

 

Discovery, 

XP95 and 

Orbis 

Multisensor 

detectors 

*See note 1

 

Discovery 

Multisensor 

detector in 

heat only 

mode 

*See note 2

 

Discovery 

CO 

*See note 3

 

Aerosol Test 
Gas (Solo 
A3) used 
with Smoke 
Detector 
Test 
Applicator 
 

 

 

 

 

 

 

 
Testifire 
 

 

 

 

 

 

 

 
Cordless 
Heat  
Detector 
Tester 

 

 

 

 

 

 

 
Mains  
Powered 
Heat  
Detector 
Tester 

 

 

 

 

 

 

 
Aerosol CO 
Test Gas 
(Solo C3) 
used with 
Smoke  
Detector 
Test 
Applicator 

 

 

 

 

 

 

Table 1

 

Summary of functional test procedures 

 
 
 

*

Note 1:

 For Orbis use ‘FastTest’  

*

Note 2:

 Discovery detectors may take up to 40 seconds to activate. 

*

Note 3:

 Discovery CO detectors may take over 60 seconds to activate dependent on setting. 

 
 
 
Testifire (Smoke, Heat and CO) 

204-0025, 204-0028 and 204-0029 

Aerosol test Gas (Solo A3) 

204-0014 

Aerosol CO Test Gas ( Solo C3) 

204-0020 

Smoke Detector Test Applicator 

204-0004 

Cordless Heat Detector Tester 

204-0017 

Mains Powered Heat Detector Tester 

204-0005 

 
 

Содержание 204-0005

Страница 1: ...Ampac Detectors Cleaning Maintenance and Functional Test Procedures MAN3069 2 ...

Страница 2: ...est Procedures for Ampac Smoke and Heat Detectors 2 2 1 Testing Ampac smoke detectors 2 2 2 Testing rate of Rise Detectors 90ºC 3 2 3 Testing Multisensor Detector 4 2 4 Testing Discovery CO Detector 5 3 Cleaning Instructions for Optical Smoke and Multisensor Detectors 7 ...

Страница 3: ...r with Ampac supplied equipment and may not be used for any other purpose whatsoever 2 The Trader shall disclose Proprietary Information received by Ampac under this Agreement to persons within its organisation only if such persons are legally bound in writing to protect the confidentiality of such Proprietary Information 3 The undertakings and obligations of the Trader under this Agreement shall ...

Страница 4: ...pplicator as per instruction manual supplied with the test equipment Place test applicator over detector ensuring seal around smoke detector Push applicator upwards slightly to activate aerosol for a one second burst If the detector has not responded in 10 seconds repeat the previous step The total number of sprays should not exceed five at 10 second intervals If the detector fails to activate che...

Страница 5: ...pole in place until the alarm is activated When the detector alarms remove the tester from the detector The tester will revert to standby mode slow flashing green LED and the internal fan will cool the heating element for a few seconds 2 2 4 Additional steps for testing Orbis heat detectors For all Orbis heat detectors even CS class place the control panel in test mode OR remove the detector from ...

Страница 6: ... elements can be tested simultaneously using this 2 3 3 For Orbis Multisensor detectors place the control panel in test mode OR remove the detector from the detector base then re fit OR reset the control panel 2 3 4 Follow steps detailed in 2 2 3 2 3 5 For quicker activation times use Testifire with combined smoke and heat test protocol 2 3 6 For XP95 Multisensor detectors follow steps detailed in...

Страница 7: ... Place CO test gas inside smoke detector test pole as per instruction manual supplied with test equipment Place applicator over CO detector ensuring seal around CO detector Press upwards slightly to activate aerosol in a one second burst If the detector has not responded in 30 seconds repeat test at 30 second intervals whereby the total number of applications should not exceed five If the detector...

Страница 8: ...h Smoke Detector Test Applicator Testifire Cordless Heat Detector Tester Mains Powered Heat Detector Tester Aerosol CO Test Gas Solo C3 used with Smoke Detector Test Applicator Table 1 Summary of functional test procedures Note 1 For Orbis use FastTest Note 2 Discovery detectors may take up to 40 seconds to activate Note 3 Discovery CO detectors may take over 60 seconds to activate dependent on se...

Страница 9: ...ssembling Use a commercial vacuum cleaner with a brush attachment to remove exterior dust and dirt and an air pressure canister Detector Duster to blow through the smoke entry points as illustrated in the image below The case can be cleaned with a dampened cloth with a solution of washing up liquid Image A cleaning a detector with a air pressure canister UNCONTROLLED DOCUMENT NOTE Due to Ampac s c...

Отзывы: