Data and Alarm Channel Configuration
The
AMG5614
sends and receives data to/from a
AMG5613
single channel standalone transmit unit.
The physical data interface RS-485, RS-422 or RS-232 is individually selectable by the user with the
corresponding slide switch mounted on the main PCB inside the enclosure.
One bi-directional alarm is also provided. The alarm input is typically connected to a contact closure
switch. The alarm output can receive an on/off signal from an
AMG5613
and is typically used to
convey contact closure status.
Data Channel Configuration
Each low speed data channel provides an RS-232, RS-422 (full duplex, four wire) or RS-485 (half
duplex, two wire) interface defined by the corresponding mode switch inside the enclosure. Every data
channel as shipped from the factory is set up for RS-485 operation unless otherwise requested.
The data input for both the RS-485 and the RS-422 modes detects a tri-state input condition by
monitoring the differential voltage level across the input. A differential level below 600mV positive or
negative will be detected as a tri-state condition. A level above 600mV positive or negative will be
detected as a logic 1 or logic 0 respectively. It is important therefore to terminate the RS-485 bus or
the RS-422 input bus using 120Ω if a pre-bias is present on the RS-485 or RS-422 bus.
A large number of third party equipment manufacturers apply a pre-bias on their RS-485 bus. This pre-
bias is applied by pulling one arm of the RS-485 bus high (+5 volts) and the other arm low (0 volts)
using high value resistors within the third party equipment. In order to ensure that the AMG equipment
detects a tri-state condition, then these resistors should have a value above 5kΩ. If the third party
bias resistors are less the 750Ω the bus can be multiple terminated as required to ensure that a tri-
state level is detected. The system detects a tri-state input condition on the data channel bus when in
RS-485 or RS-422 mode.