Data and Alarm Channel Configuration 

The 

AMG5424R 

sends and receives data to/from up to two 

AMG5413

 single channel or one 

AMG5423

 or 

AMG5423R

 rackmount equivalent dual channel

 

transmit units. Each physical data 

interface RS-485, RS-422 or RS-232 is individually selectable by the user with the corresponding slide 

switch mounted on the main PCB inside the enclosure.  

 

1 bi-directional alarm is also provided for each video channel, each of which can receive an on/off 

signal from an 

AMG5413

 and are typically used to convey contact closure status. Each alarm output 

uses a Solid-

state relay, with a maximum load current of 150mA at 125Vac/dc and Ron < 6.5Ω.

 

 

 

 

 

 

Data Channel Configuration 

Each low speed data channel provides an RS-232, RS-422 (full duplex, four wire) or RS-485 (half 

duplex, two wire) interface defined by the corresponding mode switch inside the enclosure. Every data 

channel as shipped from the factory is set up for RS-485 operation unless otherwise requested. 

 

The data input for both the RS-485 and the RS-422 modes detects a tri-state input condition by 

monitoring the differential voltage level across the input. A differential level below 600mV positive or 

negative will be detected as a tri-state condition. A level above 600mV positive or negative will be 

detected as a logic 1 or logic 0 respectively. It is important therefore to terminate the RS-485 bus or 

the RS-

422 input bus using 120Ω if a pre

-bias is present on the RS-485 or RS-422 bus.  

 

A large number of third party equipment manufacturers apply a pre-bias on their RS-485 bus. This pre-

bias is applied by pulling one arm of the RS-485 bus high (+5 volts) and the other arm low (0 volts) 

using high value resistors within the third party equipment. In order to ensure that the AMG equipment 

detects a tri-

state condition, then these resistors should have a value above 5kΩ.  If the third party 

bias resistors are less the 750Ω the bus can be multiple terminate

d as required to ensure that a tri-

state level is detected. 

 

Содержание AMG5424R

Страница 1: ...larm for a Multimode Fibre Link The AMG5424R is a DUAL rackmount data receive unit which provides two independent channels each designed to transmit and receive 1 bi directional alarm and transmit and...

Страница 2: ...ptical Connection 3 Connections 4 Optical Connections Multimode 4 Power Connection 4 Data and Alarm Channel Connections 4 Front Panel Indicators 5 Power Opto LED 5 Low Speed Data LEDs 5 Alarm LEDs 5 D...

Страница 3: ...rovides two independent receive channels Each channel receives 1 data and 1 bi directional alarm signal from up to two AMG5413 transmit units It also transmits 1 data signal to each AMG5413 The schema...

Страница 4: ...hich may restrict operation to a maximum fibre length of 7km although in most cases the units will operate successfully over longer fibre lengths It is advisable however for distances greater than 7km...

Страница 5: ...d logic transitions present on input IN Off logic one V present on input IN IN corresponds to the data signals being transmitted onto the optical fibre Data Present OUT RS485 or RS422 Green logic zero...

Страница 6: ...plex two wire interface defined by the corresponding mode switch inside the enclosure Every data channel as shipped from the factory is set up for RS 485 operation unless otherwise requested The data...

Страница 7: ...OUT B OUT B OUT Note A or B in brackets in the above table refers to RS 485 RS 422 data specification Alarm Channel Configuration The AMG5424R provides one bi directional alarm output contact closure...

Страница 8: ...ng screws on the rear panel and slide the PCB sufficiently out of the case to enable access to the switch To replace the PCB into the case slide the PCB gently into the case if necessary aligning the...