TR-2100 User Manual
75
RMS Measurement
The true RMS value for every channel is generated twice per cycle. The data for one cycle
are squared and summed. The square root is taken of this value divided by the number of
samples per cycle. The number of samples per cycle will vary with the sample rate.
96
96
1
2
∑
=
=
n
n
rms
V
V
Frequency Correction
Because the system frequency varies by small but finite amounts during normal operation,
uncorrected RMS and vector measurements will have an error that is a function of frequency
deviation. Since the TR-2100 measures the system frequency, it corrects for these errors.
For a frequency of 49.9 Hz the uncorrected errors are:
Amplitude error = 0.01%
Phase
error
=
0.7
°
Calculation of Derived Parameters
A range of fundamental quantities may be computed from the fundamental voltage and
current vectors.
Sequence components
Positive
+
−
−
−
=
+
+
1
2
3
V
V
a V
a V
a
b
−
c
−
c
−
3
Zero
0
−
−
−
=
+
+
V
V V V
a
b
Negative
−
−
−
−
=
+
+
1
2
3
V
V
a V
a V
a
b
c
V
a
−
represents the vector form of the a phase voltage
(operator
a
rotates the vector by 120
°
)
Содержание TR-2100
Страница 2: ......
Страница 6: ...iv ...
Страница 10: ...TR 2100 User Manual 4 ...
Страница 16: ...TR 2100 User Manual 10 ...
Страница 24: ...TR 2100 User Manual 18 ...
Страница 34: ...TR 2100 User Manual 28 ...
Страница 38: ...TR 2100 User Manual 32 ...
Страница 51: ...TR 2100 User Manual 45 Figure 10 Sliding Out CPU Assembly Potentiometer Figure 11 PSU Potentiometer ...
Страница 54: ...TR 2100 User Manual 48 Figure 12 Analogue Input Board Jumpers ...
Страница 78: ...TR 2100 User Manual 72 ...
Страница 94: ...TR 2100 User Manual 88 ...
Страница 98: ...TR 2100 User Manual 92 ...
Страница 99: ...TR 2100 User Manual 93 Appendix V System Drawings ...
Страница 100: ...TR 2100 User Manual 94 ...
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ......