28
UPS + Isolation User Manual
© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com
Model #: ABCE3002-21R / Part #: UPS-3000-Li-ISO
Rack Mount UPS Specifications
Front Panel Controls
Environmental
Power On/Off
Temperature: 0 - +40
0
C (32 to 104
0
F) Operating
Test
-20 to 60
0
C (-40 to 140
0
F) Shipment/
Load Level LED Gauge
Storage
Battery Charge LED Gauge
Humidity:
5 to 90% Non-Condensing (Operating,
Shipment/Storage)
Voltage Manager Boost LED
Altitude:
3,000m (10,000 ft) max. Operating;
Voltage Output On LED
12,000m (40,000 ft) max. Shipment/Storage.
Voltage Manager Buck LED
On Battery LED
Safety Agency and EMC Compliance:
Replace Battery LED
All Units are Listed by UL and Marked with the UL/cUL Marking.
Overload LED
Standard UPM:
Fault Code LED
Products Listed To:
System Over Temperature LED
UL IEC62040, CE Mark with CB Report
Rear Panel Information and Controls
Products in compliance with:
1.8 Meter Power Cord with C20 to L6-20 Plug
FCC-Part 15, Subpart B, Sections 15.107b & 15.109b
Eight (8) NEMA 5-20R and (1) NEMA L6-20 Receptacles
Class A Digital Device*
Configuration Manager DIP Switches
CISPR11:2009, A1; 2010, Class A*
Communications Manager DB9 Port, USB Port
IEC61000-4-2, Electrostatic Discharge
Circuit Breaker
IEC61000-4-3, Radiated Electromagnetic Field Immunity
AC Inlet Module
IEC61000-4-4, Electrical Fast Transient/Burst Immunity
SNMP Slot (Contact Factory)
IEC61000-4-5, Surge Immunity
IEC61000-4-6, Immunity to Conducted Radio Frequency
Internal Batteries
Disturbances
User Hot-Swappable (See Instruction Manual)
IEC61000-4-8, Power Frequency Magnetic Field Immunity
Type: 12 Volt, High Rate 23W
IEC61000-4-11, Voltage Dips, Short Interruptions, and
Quantity: 8 Batteries
Voltage Variations
Recharge Time: 8 Hours to 80%, 24 Hours to Full Charge
*Note: Class B is Available as an Option
Please Consult Your SurgeX Sales Representative
3000VA TYPICAL RUN-TIMES (MINs)
10% (248W)
20% (297W)
30% (745W)
40% (993W)
50% (1242W)
60% (1490W)
70% (1739W)
80% (1987W)
90% (2235W)
100% (2484W)
Internal Batteries Only
89
58
20
14
10
7
6
4.8
3.2
3
Internal + 1) E4804-12
239
178
62
42
30
24
16
10.8
9.2
7.5
Internal + 2) E4804-12
389
298
104
70
50
41
26
16.8
15.2
12
Internal + 3) E4804-12
539
418
146
98
70
58
36
22.8
21.2
16.5
Internal + 4) E4804-12
689
538
188
126
90
75
46
28.8
27.2
21
Internal + 5) E4804-12
839
658
230
154
110
92
56
34.8
33.2
25.5
Internal + 6) E4804-12
989
778
272
182
130
109
66
40.8
39.2
30
Internal + 7) E4804-12
1139
898
314
210
150
126
76
46.8
45.2
34.5
Internal + 8) E4804-12
1289
1018
356
238
170
143
86
52.8
51.2
39
NOISE REJECTION-ISOLATION:
With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode
at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-
NM, CM-CM, NM-COM).
SURGE VOLTAGE WITHSTAND CAP ABILITY:
Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A -
6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support:
SurgeX warrants the elec tronics and transformers used in its uninterruptib le power managers to be free from defects
in materials and workmanship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from the date
of shipment. For service or support on any SurgeX product, please contact SurgeX Technical Support at (800) 645-9721 or visit the SurgeX
website at
ww.surgex.com
.
Battery Life Disclaimer
: SurgeX
’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC
mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will
experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products
used in such applications will experience substantially reduced battery life. For that reason, SurgeX
’s standard battery warranty does not apply
for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. SurgeX UPS products used
in such applications shall receive a 90 day warranty on batteries.