Installation
Asterion DC Series
2-20
2.8.3
AC Input Connector
The AC input connector, AC INPUT, is located on the rear panel, along with the
safety-ground stud. Figure 2-11. AC Input Connector Wiring shows the wire
installation details. Table 2-2 shows the functions and connector pinout, and Table
2-3 lists the connector type.
Figure 2-11. AC Input Connector Wiring
A 1-Phase input is connected to terminals L1/L2 or L2/L3 or L1/L3, while a 3-Phase
input is connected to L1/L2/L3 (a connection to neutral is not utilized with 3-Phase
input). The connector has compression terminals with female contacts. A ground
connection must always be made to the utility earth protection ground using the AC
Input connector pin or rear panel safety-ground stud.
Name
Type
Range
Function
AC INPUT L1
AC Input
90-264 VAC
Line-1 input from utility AC mains;
For 1-Phase input, connect lines to terminals L1
and L2, or L2 and L3; or L1 and L3
AC INPUT L2
AC Input
90-264 VAC
Line-2 input from utility AC mains.
For 1-Phase input, connect lines to terminals L1
and L2, or L2 and L3; or L1 and L3
AC INPUT L3
AC Input
90-264 VAC
Line-3 input from utility AC mains;
For 1-Phase input, connect lines to terminals L1
and L2, or L2 and L3; or L1 and L3
GND
Safety
Ground
N/A
Safety-Ground connection from utility earth
protection-ground.
Table 2-2. AC Input Connector Pinout and Safety-Ground
Содержание Sorensen Asterion DC Series
Страница 1: ...M330460 01 Rev D 1 Asterion DC Series Operation Manual...
Страница 2: ...Contents Asterion DC Series ii This page intentionally left blank...
Страница 23: ...Asterion DC Series Overview M330460 01 Rev D 1 7 Figure 1 2 Auto range Models Characteristics...
Страница 38: ...Overview Asterion DC Series 1 22 This page intentionally left blank...
Страница 43: ...Asterion DC Series Installation M330460 01 Rev D 2 5 Figure 2 1 Rack mounting 1U Models...
Страница 44: ...Installation Asterion DC Series 2 6 Figure 2 2 Rack Mounting 2U Chassis...
Страница 48: ...Installation Asterion DC Series 2 10 Figure 2 4 Installation Drawing Enhanced front panel version 2U Models...
Страница 49: ...Asterion DC Series Installation M330460 01 Rev D 2 11 Figure 2 5 Rear Panel View 1U Models...
Страница 50: ...Installation Asterion DC Series 2 12 Figure 2 6 Rear Panel View 1U Models w EtherCAT Option...
Страница 51: ...Asterion DC Series Installation M330460 01 Rev D 2 13 Figure 2 7 Rear Panel View 1U Models w GPIB Option...
Страница 52: ...Installation Asterion DC Series 2 14 Figure 2 8 Rear Panel View 2U Chassis...
Страница 83: ...Asterion DC Series Installation M330460 01 Rev D 2 45 This page intentionally left blank...
Страница 84: ......
Страница 144: ...Calibration Asterion DC Series 3 60 Figure 3 114 Parallel Connection 3 Chassis...
Страница 145: ...Asterion DC Series Calibration M330460 01 Rev D 3 61 Figure 3 115 Parallel Connection 2 Chassis...
Страница 148: ...Calibration Asterion DC Series 3 64 Figure 3 117 Series Connection...
Страница 149: ...Asterion DC Series Calibration M330460 01 Rev D 3 1 This page intentionally left blank...
Страница 151: ...Asterion DC Series Calibration M330460 01 Rev D 4 3 This page intentionally left blank...
Страница 152: ......
Страница 157: ...M330460 01 www powerandtest com This page intentionally left blank...