9.7 Protection function and fault output  

      OUT2

The protection function serves for protecting the motor 

against destruction e.g. at external strain. Confirma-

ble protection functions turn off the output stage when 

achieving a marginal value. This is announced by the 

fault-output OUT2. The output is performed as a PNP-

transistor 24 V-pulse switching, with a max. permissi

-

ble current strain of 250 mA. Thereby, following logic 

is essential:

/fault

Description

0

fault

1

no fault

For confirmation of a fault message, the motor must 

be set into status “OFF” (IN0, IN1 = 0). If the cause 

of fault is debugged (e.g. switch-on voltage threshold 

achieved, temperature o.k.), this is shown via OUT2 = 

1, and the motor can be started again.

Protection 

function

Type

Range

Confir-

mati-

on?

Availa-

ble?

Over-tem-

perature 

Soft-

ware

110 °C off,

100 °C on

Yes

Yes

Under-

voltage 

Logic

Soft-

ware

16,5 V off,

18,5 V on

Yes

Yes

Under-

voltage 

motor

Soft-

ware

7 V out,

8 V on

Yes

Yes

9.7 Schutzfunktionen und Meldeausgang  

      OUT2

Die Schutzfunktionen dienen dem Schutz des Motors 

vor Zerstörung z.B. bei extremer Belastung. Quittier-

bare Schutzfunktionen schalten die Endstufe bei Er

-

reichen eines Schwellwertes ab. Dies wird durch den 

fault-Meldeausgang OUT2 angezeigt. Der Ausgang ist 

als PNP-Transistor 24 V-plusschaltend mit einer max. 

zulässigen Strombelastung von 250 mA ausgeführt.  

Dabei gilt folgende Logik:

/fault

Bedeutung

0

Störung

1

Keine Störung

Zur Quittierung einer Störmeldung muss der Motor in 

den Zustand „AUS“ (IN0, IN1 = 0) versetzt werden.

Ist die Fehlerursache beseitigt (z.B. Einschaltspan-

nungsschwelle erreicht, Temperatur o.k.), wird dies 

durch OUT2 = 1 angezeigt und der Motor kann wieder 

gestartet werden.

Schutz

-

funktion

Art

Bereich

Quit-

tie-

rung?

Vor

-

han-

den?

Übertem-

peratur

Soft-

ware

110 °C aus,

100 °C ein

Ja

Ja

Unter-

spannung 

Logik

Soft-

ware

16,5 V aus,

18,5 V ein

Ja

Ja

Unter-

spannung 

Motor

Soft-

ware

7 V aus,

8 V ein

Ja

Ja

Содержание dunkermotoren BG 75 SI Series

Страница 1: ...Edition Ausgabe 05 2017 Instruction Manual Betriebsanleitung BLDC motor with integrated speed controller EC Motor mit integriertem Drehzahlregler BG 75 SI...

Страница 2: ...ly 23 8 3 Connection signal interface supply 23 9 Operation hints 24 9 1 Operation 25 9 2 Function of the digital inputs IN0 and IN1 25 Seite 1 Inhalt 2 2 ber dieses Dokument 4 3 Allgemeine Beschreibu...

Страница 3: ...vice and disposal 33 10 2 Service Support 33 10 3 Scope of delivery and accessories 34 10 4 Download PDF Data 34 11 Appendix 35 A CE declaration of the manufacturer 35 9 3 Funktion der Digitaleing nge...

Страница 4: ...anger to persons or damage to the machine Disconnect the electrical power supply Vor der Inbetriebnahme sind unbe dingt die Sicherheitshinweise zu lesen und zu beachten Eine Nichtbeach tung kann zu Ge...

Страница 5: ...with special firmware are available on request The motor has except of the ball bearings no expen dable parts and is hence excellently suited for conti nuous operation The motors BG 75 SI can be com b...

Страница 6: ...o operation once the entire system has been installed in accordance with EMC Please follow the instructions in chapter 7 2 3 2 Begriffserkl rungen Br ckengleichrich ter Bauteil zur Umwandlung von Wech...

Страница 7: ...complies with the safety standards listed therein and with EMC standards The product may be sold and used within the European Union 3 4 Normen und Richtlinien EG Richtlinien Die EG Richtlinien formul...

Страница 8: ...Betrieb setzen und installieren darf HINWEIS The drive must only be installed and adjusted by qualified persons in accordance with the relevant standards Qualified persons are those who on the basis o...

Страница 9: ...up to 30 C motor 50 A Max peak current up to 100 C motor 30 A Current consumption of 24 V logic supply 70 mA power of digital outputs 5 Technische Daten Zubeh r 5 1 Elektrische Daten Regelbarer Drehz...

Страница 10: ...haft outlet has been installed such that it is protected from dust and water Please see the pin diagram for further information 5 3 Dimensions 5 2 Mechanische Daten Temperaturbereich Motor 20 C 100 C...

Страница 11: ...n accordance with VDE the German Electrical Engi neers Association EN European Standard and taken during the installation of a thermally conductive steel plate with the dimensions 105x105x10mm data in...

Страница 12: ...fitted with an attached absolute encoder The signals of the SI only can be evaluated externally 5 7 Optionale Anbauten Schneckengetriebe SG Die Schneckengetriebe zeichnen sich durch hohe Laufruhe aus...

Страница 13: ...imitation To protect the motor against overloading the motor current phase current will be supervised from a I2 t protective function and will be limited if necessary 6 Schutzfunktionen Schutzfunktion...

Страница 14: ...anen Oberfl che befestigt werden Die Flansch schrauben m ssen mit Federscheiben gegen Verdre hen gesch tzt werden Die Motorabtriebswelle darf mit maximal 90 bzw 130 N radial oder axial belastet werden...

Страница 15: ...ile Ferrite oder Filtermodule Zus tzliche Speicherkondensatoren Vor dem Betrieb muss die elektromagnetische Vertr g lichkeit der Maschine gepr ft und sichergestellt wer den 7 3 Schutzleiter Anschluss...

Страница 16: ...Intercontec Der 4 polige Stecker dient zur Leistungsversorgung des Motors Ste cker Pin Anschluss Litzenfarbe der Anschlusslei tung mit 4pol Winkelstecker 1 1 motor power schwarz 2 Ballastwi derstand s...

Страница 17: ...lug to DIN 45326 Binder Series 723 The 12pin motor connector is for logic supply of the motor Gegenstecker mit Anschlu leitung bitte mitbestellen F r die Motoren BG 75 SI mit 4 poligem Anschlu ste cke...

Страница 18: ...V Bezugsmasse f r Uc schwarz L Service Service Schnittstelle rot blau M Service wei Litzenfarben beziehen sich auf Standard An schlussleitungen von Dunkermotoren Connec tor Pin Connec tion Function St...

Страница 19: ...ung bitte mitbestellen F r die Motoren BG 75 CI mit 12 poligemAnschlu stecker stehen passende vorkonfektionierteAnschlu leitungen in verschiedenen L ngen ab Lager zur Verf gung Die Leitungen sind auf...

Страница 20: ...nung V Max current max Strom A Conductor cross section Leiterquer schnitt mm2 Max recom mended cable length max empfohlene Kabell nge m Standard cable length Standard Kabell nge Order numb er cable B...

Страница 21: ...en VORSICHT Incorrect connection of motor power electronics The motor is not equipped with reverse polarity protection Consequence Destroying of the power electronics possible Check the right polarity...

Страница 22: ...iles oder wie im nachfol genden Prinzipschaltbild erfolgen Der grau hinterlegte Ausschnitt des Prinzipschalt bildes zeigt die exakten Anschl sse eines BG75 SI Es k nnen auch mehrere BG Motoren wie dar...

Страница 23: ...lenversorgung L und M sind nicht belegt A B C D E F G H L M Uc 24 V Logik Logic GND 0V Logik Logic yellow gelb blue blau brown braun green g r n grey grau grey pink grau rosa pink rosa violet violett...

Страница 24: ...larit t und H he der Versorgungsspannung achten Erst danach die Steuer eing nge IN0 IN1 und ggf die Sollwertspannung zur Drehzahlvorgabe beschalten Hinweis Der Motor soll nicht ber die Versorgungsspan...

Страница 25: ...t to each of the both inputs the logical states 0 and 1 are dedicated 0 complies with an input level of 0 6 V 1 complies with an input level of 7 24 V 9 2 Funktion der Digitaleing nge IN0 und IN1 Mit...

Страница 26: ...ain via separating from the supply voltage To teach the second fixed speed repeat this proce dure Die folgenden Betriebszust nde k nnen angesteuert werden IN2 IN3 Funktion 0 0 Drehzahlregelbetrieb 0 1...

Страница 27: ...ter For clarification some values are presented in table form see next page 9 5 Teachen von Rampen Falls der Motor die Option bietet Eing nge IN2 IN3 herausgef hrt k nnen die Beschleunigungs und Brems...

Страница 28: ...otor again via separating from the supply voltage To teach the second ramp repeat this procedure US Volt z 1024 U 10 Zahl T ms pro 1000 rpm 0 0 20000 2 205 16004 4 410 12008 6 614 8012 8 819 4016 9 92...

Страница 29: ...rotation of n rpm The output is performed as PNP transistor 24 V plus switching with a max permitted current strain of 250 mA 9 6 Funktion des Pulsausgangs OUT1 Der Pulsausgang OUT1 liefert 12 Impuls...

Страница 30: ...e Soft ware 110 C off 100 C on Yes Yes Under voltage Logic Soft ware 16 5 V off 18 5 V on Yes Yes Under voltage motor Soft ware 7 V out 8 V on Yes Yes 9 7 Schutzfunktionen und Meldeausgang OUT2 Die Sc...

Страница 31: ...Set value voltages over 10 V are allowed but do not effect any increase of motor speed Note A not connected analogue input equals 0 rpm 9 8 Funktion des Analogeinganges AI AI Die Eingangsschaltung des...

Страница 32: ...laufdiode ist gem nachfolgender Skizze einzubauen Abbildung 4 Abbildung 5 Kontaktabbrand und Spannungs spitzen bei Motoren mit angebauter Bremse Die Folge Zerst rung elektrischer Bauteile Freilaufdiod...

Страница 33: ...ort portal at www dunkermotoren de support Ankerstoppbremse mit 6 pol Anschlussstecker Pin Anschluss 1 24 V f r Bremse 2 0 V f r Bremse 3 n c 4 n c 5 n c 6 n c 10 Wartung Service 10 1 Wartung Ausserbe...

Страница 34: ...elephone 49 7703 930 0 Fax 49 7703 930 210 E Mail info dunkermotoren de 10 3 Scope of delivery and accessories As quoted 10 4 Download PDF Data www dunkermotoren de Die PDF Datei dieser Betriebsanleit...

Отзывы: