DR22
X
0 Radar Level Instrument
10
Function ( Fct.)
Input range
Description
If YES, for every access a 9-
digit entry code on the 4
keys is necessary.
3.4.3
CODE 1
Enter code (RRREEEUUU )
Enter the entry code for
access lockout.
3.4.4
LOCATION
Enter text (8 characters)
Enter a device identifier.
3.5
APPLICAT.
3.5.1
AUTO TANKH.
Special function
Automatic determination of
tank height
(see explanatory notes).
3.5.2
EMPTY.SPEC.
Select OFF/ON/
RECORD
Recording the profile of the
empty tank (empty-tank
spectrum) (see explanatory
notes).
3.5.3
TIMECONST.
Value 1...10...100 [s]
Enter time constant for
measured-value filtering
3.5.4
TRACING.VEL.
Value
0.01...0.50...10.00 [m/Min]
Enter the maximum rate of
change in level that can
occur in operation.
3.5.5
MULT.REFL.
Select NO/YES
Switch the multi-reflection
identifier on/off.
3.5.6
BD-DETECT.
Select NO/YES
Switch the block distance
(overfill) identifier on/off
(see explanatory notes).
3.5.7
FUNCT. FTB
Select OFF/
PARTIAL
Select function of tank
bottom tracing system (see
explanatory notes).
3.5.8
EPSILON R
Enter
1.1000 ... 8.0000
Enter relative permittivity of
product (only for Fct. 3.5.7)
3.5.9
TANKTYPE
Select STORAGE T. /
PROC TANK
Select tank type.
STORAGE T. = smooth
product surface
PROC TANK = slightly
disturbed pro duct surface
Configuration menu (version 7.00) (cont.)