Installation
23
2.8
Loop Configuration of 4mA & 20mA Control Points
Loop configuration of 4mA and 20mA control points can
be set either outside the vessel or within the vessel. If the
configuration is set inside the vessel, then actual level position
within the vessel is used to set the 4mA and 20mA positions.
If this is not practical, the probe should be “Bench Configured”.
The system requires Intrinsically Safe power, so setting the Zero
and Span points can be done in a hazardous area.
2.8.1
Manually
1.) Power-up the probe
2.) Place float at desired 4mA / 20mA position
3.) Unlock the configuration program by momentarily “Shorting”
the White Program Wire (Blue in EU) to the Black Loop "-"
Wire (Based on the security timing sequence in Section
2.8.3)
4.) The 4mA control point is set by momentarily “Shorting” the
White Program Wire (Blue in EU) to the Black Loop "-" Wire
(Based on the security timing sequence in Section 2.8.3)
5.) The 20mA control point is set by momentarily “Shorting”
the White Program Wire (Blue in EU) to the Red Loop "+"
Wire (Brown in EU) (Based on the security timing sequence
in Section 2.8.3)
6.) Loop configuration is complete
3
2
4
1
CHASSIS
(Sheild for Cable)
(Green wire for cord set)
LOOP IN (–)
(Black wire)
PROGRAM INPUT
(White wire)
LOOP IN (+)
(Red wire)
Figure 2-16
"M" Probe Connector
ZERO
SPAN
+
–
PROGRAMMING
BUTTONS
ZERO
SPAN
Figure 2-17
"H" Housing Option
Содержание DM330 Series
Страница 4: ......
Страница 6: ...Section 1 ...
Страница 12: ...Section 2 ...
Страница 32: ...Section 3 ...
Страница 34: ...Section 4 ...
Страница 40: ...Section 6 ...
Страница 42: ...DM330 Series Magnetostrictive Level System User s Manual 36 6 2 EC Declaration of Conformity ...
Страница 43: ...Control Drawings 37 Section 7 Control Drawings ...
Страница 44: ...DM330 Series Magnetostrictive Level System User s Manual 38 Section 7 Control Drawings Continued ...
Страница 45: ......
Страница 47: ......