Sequence
The alarm sequence for each input group is defined in this page. The Input
Configuration page was used to indicate which of the four available groups was
assigned to each input. This page identifies the sequence chosen for each
group.
Note:
The four available groups can be set up for the same First-Out Sequence,
but each group is treated separately as its own first out group.
To change the alarm sequence, click on the entry then choose the sequence
from the list. The alarm sequences shown below follow ISA Standard S18.1 –
1979 (R.1985).
ISA-A
Automatic reset with lock-in of alarms
ISA-A-4
Automatic reset with no lock-in of alarms
ISA-A-4-5-6
Automatic reset, non-locking, no flash, no audible, NO PB
ISA-M
Manual Reset with lock-in of alarms
ISA-F1A-1
First Out Flash, Subsequent alarm steady, auto reset
ISA-F2A-1
First Out, Fast Flash, auto reset
ISA-F2M-1
First Out, no subsequent alarm flash, manual reset
ISA-F3A
First Out, triple flash, first out reset
ISA-F3M
First out, triple flash, first out manual reset
ISA-F3C
First out, triple flash, dual color, manual reset
ISA-FFAM2
First Out, manual reset
ISA-R
Ringback, separate flash for return to normal
ISA-RC
Ringback, separate color for return to normal
ISA-R-12
Automatic Momentary Ringback, dual flash, manual reset
ISA-R-12C
Ringback, dual color flash, manual reset