INSTALLATION
4
-
2 November 17, 2020
Table 4
-
1 Recommended AC Input and Branch Fusing
LINE
AMPS
DISCONNECT
SWITCH *
COPPER CABLE SIZE AWG * *
BRANCH FUSE
SIZE (AMPERES)
POWER
GROUND
0
-
2.5
30A
5
No. 14
No. 14
2.6
-
4.5
30A
7
No. 14
No. 14
4.6
-
7.5
30A
10
No. 14
No. 14
7.6
-
12
30A
15
No. 14
No. 14
12.1
-
16
30A
20
No. 12
No. 12
16.1
-
18
30A
25
No. 10
No. 10
18.1
-
22
30A
30
No. 10
No. 10
22.1
-
24.5
60A
35
No. 8
No. 10
24.6
-
32.5
60A
40
No. 8
No. 10
32.6
-
40
60A
50
No. 8
No. 10
40.1
-
45
60A
60
No. 6
No. 10
45.1
-
57.5
100A
80
No. 4
No. 8
57.6
-
78
100A
100
No. 2
No. 8
78.1
-
102.5
200A
125
No. 2
No. 6
102.6
-
135
200A
150
No. 1/0
No. 6
The above table (Table 4
-
1) is based on 75°C (167°F) rated conductors and 40°C (104°F) ambient temperatures. Refer to
National Electrical Code (2008) Tables 310
-
16 corrected to 40°C (104°F).
* For 115, 208, and 230
-
volt lines, use 250
-
volt disconnect switch.
For 440
-
480, 575
-
volt lines, use 600
-
volt disconnect switch.
* * Two conductors and ground conductor required for single phase.
Three conductors and ground conductor required for three phase.
Recommended minimum size of grounding conductors (based on National Electrical Code 2008 –
Table 250
-
95).
Line Voltage Changeover
Instructions
1. Determine if the charger is connected for available
line voltage. A label located near AC input terminals
is marked with the AC voltage for which the charger
is factory connected.
2. If charger is not connected correctly, check serial
nameplate to determine that charger is equipped
to be connected for available line voltage. If
charger is suitably equipped, make voltage change
-
over connections by following instructions on AC
INPUT label inside charger.
3. If charger is reconnected, check input fuse (s)
ratings with ratings specified on label and replace
if necessary.
CAUTION: INCORRECT CONNECTIONS
AND INCORRECT FUSE SIZE can damage
this equipment. Follow voltage changeover
instructions carefully.
Line Connections to Battery Charger
Follow local code requirements if different than
instructions in this manual.
1. Turn charger OFF.
2. Be sure charger is connected correctly for available
line voltage as instructed above.
3. On charger nameplate, note the AC input amperes
corresponding to the line voltage to which charger
is to be connected. Use that ampere value to select
the proper disconnect switch, fuse, and power cable
sizes from Table 4
-
1. A
“
WARNING
”
label inside
charger also lists fuse sizes for each line voltage
(circled fuse rating is required for internal line
voltage connections made at factory).
Содержание AC1000 Control
Страница 2: ......
Страница 4: ......
Страница 6: ...November 17 2020 193111 055 TABLE OF CONTENTS This page intentionally left blank...
Страница 8: ...193111 055 INTRODUCTION 1 2 November 17 2020 This page intentionally left blank...
Страница 12: ...193111 055 DESCRIPTION OF EQUIPMENT 3 2 November 17 2020 This page intentionally left blank...
Страница 19: ...193111 055 OPERATION November 17 2020 5 4 Figure 5 1...
Страница 30: ...193111 055 PARTS LIST 8 1 November 17 2020 Figure 8 1 A Case...
Страница 32: ...8 3 November 17 2020 193111 055 PARTS LIST Figure 8 2 B Case...
Страница 34: ...193111 055 PARTS LIST 8 5 November 17 2020 Figure 8 3 C Case...
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ...SCHEMATIC LEGEND NOTES...
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 50: ......