May 13, 2011  Revised                                                                                                                                   4-1 

193111-078 

OPERATION 

OPERATION 

     NOTE:  If this charger is equipped with 
     certain optional features, the operating 
     procedure may be modified.  Refer to  
    OPTIONS section of this manual for 
    details.  Options not covered in this  
    section will be described on separate 
    “addendum” sheets enclosed with the 
    manual.

 

 
Preliminary 

 

1.  Make sure that charger is installed and grounded 
     as instructed in this manual. 

 

2.  Maintain electrolyte level in batteries to be  
     charged, as instructed by battery manufacturer.   
     The volume of electrolyte will expand during the  
     charge.  Therefore, to avoid overfilling, do not add  
     water until the battery has received at least an  
     80% charge.  This will usually be reached at the  
     time gassing starts. 
 
3.  Securely engage battery and charger connectors. 
 
 
     

WARNING:  EXPLOSION HAZARD - 

     Do not connect or disconnect a battery 
     unless the Charge Control/Timer  
     switch is in OFF position and Pilot  
     Light is off, and Ammeter reads zero; 
     otherwise, arcing and burning of 
     connector parts or a battery explosion 
     may result (batteries produce  explosive 
     gases).  Keep sparks, flame, and 
     cigarettes away.  Ventilate when  
     charging in an enclosed area.  Always 
     shield eyes when working near batteries. 
     Do not turn timer switch ON when no 
     battery is connected.  Disconnect 
     battery if charger is to be turned off 
     for prolonged periods of time. 

 
 
4.  On charger nameplate, note number of cells and 
     ampere-hour capacity of batteries it will charge. 
     The Multi-Range chargers are designed to  
     recharge lead-acid batteries of 6,12,18,24, or 36 
     cells of various capacities in 8 to 24 hours. 
 

 
    A..  Output Voltage Selection – A cell selector  
           switch is located inside the unit for adjusting 
           the output for 6,12,18,24, or 36 cell batteries. 
 
           

NOTE:  The cell selector must be set for 

           the same number of cells as the battery 
           to be charged.

 

 
     B.  Ampere-Hour Capacity Selection –  The  
          charging current automatically tapers on all cell 
          settings; however, the starting current will vary 
          between settings, as shown in the following 
          table: 
 
             CELL           50 AMP          75 AMP 
          SETTING       MODEL          MODEL 
 
                 6                  50                  75 
               12                  40                  60 
               18                  30                  45 
               24                  25                  38 
               36                  18                  28 
 
5.  Turn  ON main fused disconnect switch that  
     supplies AC power to charger. 
 
      

Note:  Charging cycle can be stopped at 

      any point by pressing the stop switch. 
       
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание 500882-001

Страница 1: ...instructions before installing operating or servicing this system Multi Range Silicon Diode Ferroresonant Transformer type Battery Charger 500882 001 500883 001 DO NOT DESTROY AMETEK PRESTOLITE POWER...

Страница 2: ...ructed in Maintenance section of this manual Replace any precautionary or instruction label that cannot be easily read Table of Contents SAFETY INSTRUCTIONS AND WARNINGS 1 INSTRUCTIONS 2 Receipt of Eq...

Страница 3: ...e input power phase and number of cells in battery for which charger is intended The following example explains the basic model numbering arrangement Model 380 A 1 6 S 6 Number of Circuits 1 through 6...

Страница 4: ...tional Electrical Code NFPA 70 and local codes A power disconnect switch must be located at the equipment Check nameplate for voltage and phase requirements If only 3 phase power is available connect...

Страница 5: ...he battery If the charger is equipped with an ammeter the ammeter should not indicate current flow Always connect battery before turning charger ON F Medical And First Aid Treatment First aid faciliti...

Страница 6: ...on voltage will be present on the charger output leads if the battery is disconnected before the charge is terminated CAUTION The Manual Stop switch should always be used to prematurely end a charge c...

Страница 7: ...e to make a good electrical connection Connect other end of grounding conductor to the system ground If for any reason an input cable which does not in clude a grounding conductor is used the equipmen...

Страница 8: ...le 250 95 Line Connections to Battery Charger Follow local code requirements if different than instructions in this manual 1 Turn charger OFF 2 Be sure charger is connected correctly for avail able li...

Страница 9: ...may be modified Refer to OPTIONS chapter of this manual for details Pre operation Checks 1 Inspect charger thoroughly for damage loose screws nuts or electrical connections WARNING ELECTRICAL SHOCK H...

Страница 10: ...plosion may result batteries produce explosive gases Keep sparks flame and cigarettes away Ventilate when charging in an enclosed area Always shield eyes when working near batteries Do not turn timer...

Страница 11: ...LE Charging a 6 cell 450 AH battery on a 50 Amp charger set timer to approximately 13 hours and on a 75 Amp charger set timer to approximately 10 hours D On succeeding charge cycles increase or decrea...

Страница 12: ...March 1 2008 4 3 193111 078 OPERATION...

Страница 13: ...replaced to protect personnel from contact with hazardous voltages Lubrication None required Charging Rate Adjustment Although it is normally not required the charging rate can be adjusted to accommod...

Страница 14: ...ype fuse besides the fast clearing type may cause damage to silicon diodes Silicon Diode Testing WARNING ELECTRICAL SHOCK HAZARD Before checking electrical components turn OFF and remove fuses of disc...

Страница 15: ...ilar within 20 and of a relatively high value Suppressor is bad if resistance readings are infinitely high or very low Capacitor Testing 1 Heed WARNING in Silicon Diode Testing section 2 Disconnect ca...

Страница 16: ...r inspection procedure Refer to Connection Schematic Diagram in the Diagrams chapter included in this manual Troubleshooting Guide Control Display not working Check line voltage Close fused disconnect...

Страница 17: ...tions in Installation section Less than rated output on fully discharged battery approximately 1 2 rated output 3 phase chargers only Check input fuses one probably blown Check for either a shorted tr...

Страница 18: ...ting Kit 7 1 055 Booted Alligator Clips 7 1 Portable Mounting Kit This option includes wheels and handle shipped loose Kit also includes 8 ft 2 438 m of AC cable complete with plug 50 Amp 393699 1 75...

Страница 19: ...193111 078 PARTS LIST 8 1 March 1 2008 Typical A Case Shown For Parts Designation...

Страница 20: ...93114 Insulator Fuse Shunt 20 392458 Bus Bar 21 193125 001 Shunt Meter 22 See Table Fuse Output 23 See Table Block Input Fuse 24 See Table Fuse Input 25 406240 001 Contactor AC Input 26 402832 003 Dio...

Страница 21: ...193111 078 PARTS LIST 8 3 March 1 2008...

Страница 22: ...January 15 2001 193111 078 DIAGRAMS DIAGRAMS SPECIFICATION NO DIAGRAM DIMENSIONAL OUTLINE 500882 001 398213 197203 500883 001 398213 197203 MODEL NUMBER 50A1 6M36 75A1 6M36...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Отзывы: