April 3, 2000 5-1
193111-038
INSTALLATION
INSTALLATION
A. Location
FIRE HAZARD – As with any electrical
power equipment, do not install on or
over combustible materials. Keep
charging area clear of combustible
materials.
The charger must be installed indoors. Avoid locations
exposed to high humidity, dust or ambient tempera-
tures above 40°C. (104°F.)
Adequate air circulation is required to insure proper
operation and long life. A minimum of 6 inches of free
air space should be provided at both sides and rear of
cabinet.
B. Safety
Refer to additional installation instructions under the
SAFETY INSTRUCTIONS AND WARNINGS chapter
included in this manual.
C. Grounding
The charger is provided with a 3 prong, grounding type
plug on the AC input cord. The plug must only be used
with a properly installed and grounded mating
receptacle to insure user safety. It is the responsibility
of the user to provide such a receptacle and that its
installation meets all appropriate electrical codes.
D. Electrical Input Requirements
The AC input voltage and line draw is provided on a
data plate located on the front (or rear) of the charger.
The charger is provided with the proper AC cord and
plug. Connect the AC input plug to an appropriate
receptacle that is properly grounded and protected for
15 amperes (by a branch circuit fuse (s) or circuit
breaker) (20 amperes for model 400-18). It is strongly
recommended that the charger be the only equipment
plugged into the branch supply circuit.
NOTE: Nuisance opening of branch circuit
fuses or circuit breaker may result if equipment
other than the charger is connected to the
branch circuit.
E. AC Input Voltage Changeover
120 VOLTS AC INPUT MODELS
No AC input voltage changeover is required.
208/240 & 220/380 VAC INPUT MODELS
All 208/240 & 220/380 volts AC input models are
shipped connected for a 240 or 380 volts AC input
service respectively. For 208 or 220 volts AC input
service, the charger must be reconnected as
follows:
WARNING: ELECTRICAL SHOCK CAN BE
FATAL! Be sure charger is unplugged from
AC input power and battery is disconnected
from charger before proceeding.
1. Remove the one piece top and sides.
2. Locate the terminal block (TB1) mounted on top of
the ferroresonant power transformer.
3. Move the black wire from TB1, terminal 9 to TB1,
terminal 8. Be sure the female terminal on the
black wire is fully seated on the terminal block tab.
See Figure 4-1.