AMES Colt Series Скачать руководство пользователя страница 3

3

Prior to servicing any Ames valve, it is mandatory to
shut down the water system by closing both the inlet
and outlet shutoff valves. After shutoff valves are closed,
open test cock #2, #3 and #4 to relieve pressure within
the backflow assembly.

1.  After #3 test cock has been opened to relieve pressure,

remove #3 test cock from housing. (Figure A)

2.  Insert a #3 screwdriver through the hole on the top of the

cover sleeve and using both hands rotate the cover sleeve
approximately 

1

/

4

-turn clockwise and 

1

/

4

-turn counter-clock-

wise to break the sleeve O-ring seals. Using the screwdriver,
slowly slide the cover sleeve to the downstream side of the
housing. (Figure B)

3.  Remove the stainless steel check retainer from the housing.

(Figure B)

4.  Remove the #1 check module (Figure C) by inserting two

flat blade screwdrivers into the slots on either side of the
check module and gently pry the check module toward
the open zone. 

5.  Remove #2 check module with the same instructions as

in #4 above. For servicing 6" (150mm) checks see 8" – 10"
(200 – 250mm) instructions on p.4.

6.  To clean or inspect either check module, insert a #3 screw-

driver through the downstream side of the check module
as shown in Figures D and E. When the screwdriver is in
place, remove the E-clip (Figure F) and pin connecting the
structural members and the check clapper will open with
no tension.

7.  Thoroughly clean the seating area. The sealing disc may be

removed, if necessary, by removing the screws connecting
the keeper plate to the clapper. The sealing disc may be
reversed and reinstalled if the elastomer is cut or damaged.

8.  Wash check module and O-ring and inspect for any

damage. If damaged, reinstall new parts.

9.  After thorough cleaning, lubricate O-ring w/FDA approved

lubricant, replace pin and E-clip in structural members,
remove screw driver, reinstall check modules and
assemble housing in reverse order of these instructions.

Figure D

Figure E

Figure F

Figure A

Figure B

Figure C

Figure D

Figure E

Figure F

#1 Check Diagrams

#2 Check Diagrams

Maintenance Instructions 2

1

/

2

" – 6" (65 – 150mm)

Instructions

Содержание Colt Series

Страница 1: ...ECT TO THE PRODUCT THE COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and...

Страница 2: ...ty approves the installation 3 The assembly should be installed with adequate clearance around the valve to allow for inspection testing and servicing 12 300mm should be the minimum clearance between the lower portion of the assembly and the floor or grade The valve should be protected from freezing 4 Installing a backflow preventer in a pit or vault is not recommended 5 Normal discharge and nuisa...

Страница 3: ...eck module with the same instructions as in 4 above For servicing 6 150mm checks see 8 10 200 250mm instructions on p 4 6 To clean or inspect either check module insert a 3 screw driver through the downstream side of the check module as shown in Figures D and E When the screwdriver is in place remove the E clip Figure F and pin connecting the structural members and the check clapper will open with...

Страница 4: ... until it contacts the linkage Figure A 4 Continue to thread in service bolt with the wrench until the service hole in the linkage is aligned with the service notches on the spring arbors Figure A 5 Insert the Phillips screwdriver through the arbors and service hole of the linkage making sure that the tip of the screwdriver extends past the ends of the arbors by a minimum of 1 4 6mm Figure B 6 Bac...

Страница 5: ...ness Requirements Valve must be tight against reverse flow under all pressure differentials Close high valve A and open test cock 2 Close test cock 4 Disconnect vent hose at test cock 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressure differential gauge If there is a decrease in the indicated value check valve No ...

Страница 6: ...uard only 7018894 7018894 7018894 NS O ring 3 Test Cock 7017897 7017897 7017897 NS Stainless Steel Check Retainer 7018408 7018408 7018408 ITEM DESCRIPTION ORDERING ORDERING ORDERING NO CODE 6 150MM CODE 8 200MM CODE 10 250MM 1 First Check Module EPDM 7018115 1 First Check Module Red Silicone 7018761 7018118 7018401 2 Second Check Module a EPDM 7018121 2 Second Check Module a Red Silicone 7018765 7...

Страница 7: ...ir or replace hose Relief Valve Replacement Parts Listing ITEM DESCRIPTION ORDERING NO CODE 1 Relief Valve Assembly 7018107 2 Diaphragm RV 7017809 3 Spring RV 7013368 4 Spider Bushing RV 7017811 5 Piston Assembly RV 7018227 6 Body RV 7018889 7 Hose Cover Plate Assembly 7018228 8 Screw Cover RV 7017822 9 O ring Inlet coupler 7017826 10 E Clip 5 per pack 7017870 NS Sensing Elbow 7018888 ITEM DESCRIP...

Страница 8: ...rks 2009 www amesfirewater com A Division of Watts Water Technologies Inc USA Backflow 1427 N Market Blvd Suite 9 Sacramento CA 95834 T 916 928 0123 F 916 928 9333 Control Valves 18550 Hansen Road Houston TX 77075 T 713 943 0688 F 713 944 9445 Canada 5435 North Service Rd Burlington ONT L7L 5H7 T 905 332 4090 F 905 332 7068 ...

Отзывы: