AMES Colt Series Скачать руководство пользователя страница 1

RP/IS-A-C400/C500

Reduced Pressure 
Zone Assemblies

Reduced Pressure
Detector Assemblies

Sizes: 2

1

2

" – 10" (65 – 250mm)

• Installation
• Service
• Repair Kits
• Maintenance

For other repair kits and service parts,
send for Ames Repair Parts Price List,
PL-A-RP-BPD.

For technical assistance, contact your
local Ames representative.

IMPORTANT: Inquire with governing
authorities for local installation requirements.

NOTE: For Australia and New Zealand, line
strainers should be installed between the
upstream shutoff valve and the inlet of the
backflow preventer.

Colt

Series C400, C500

It’s important that this device be tested
periodically in compliance with local codes,
but at least once per year or more as service
conditions warrant. If installed on a fire
sprinkler system, all mechanical checks,
such as alarm checks and backflow
preventers, should be flow tested and
inspected internally in accordance with NFPA
13 and NFPA 25.

C400 OSY

Installation Note: 

Due to shipping, storage,

and general handling, the Victaulic Coupling
for the shutoff valves may have loosened
and should be retightened during installation.

Limited Warranty:

Ames Fire & Waterworks (the “Company”) warrants each product to be free from defects in material and

workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within
the warranty period, the Company will, at its option, replace or recondition the product without charge.

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH
RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY
SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty,
and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost
profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs
resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water
conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by
any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation
of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you
specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights.

SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT

BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,
ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

www.amesfirewater.com

A Division of Watts Water Technologies, Inc.

Содержание Colt Series

Страница 1: ...ECT TO THE PRODUCT THE COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and...

Страница 2: ...ty approves the installation 3 The assembly should be installed with adequate clearance around the valve to allow for inspection testing and servicing 12 300mm should be the minimum clearance between the lower portion of the assembly and the floor or grade The valve should be protected from freezing 4 Installing a backflow preventer in a pit or vault is not recommended 5 Normal discharge and nuisa...

Страница 3: ...eck module with the same instructions as in 4 above For servicing 6 150mm checks see 8 10 200 250mm instructions on p 4 6 To clean or inspect either check module insert a 3 screw driver through the downstream side of the check module as shown in Figures D and E When the screwdriver is in place remove the E clip Figure F and pin connecting the structural members and the check clapper will open with...

Страница 4: ... until it contacts the linkage Figure A 4 Continue to thread in service bolt with the wrench until the service hole in the linkage is aligned with the service notches on the spring arbors Figure A 5 Insert the Phillips screwdriver through the arbors and service hole of the linkage making sure that the tip of the screwdriver extends past the ends of the arbors by a minimum of 1 4 6mm Figure B 6 Bac...

Страница 5: ...ness Requirements Valve must be tight against reverse flow under all pressure differentials Close high valve A and open test cock 2 Close test cock 4 Disconnect vent hose at test cock 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressure differential gauge If there is a decrease in the indicated value check valve No ...

Страница 6: ...uard only 7018894 7018894 7018894 NS O ring 3 Test Cock 7017897 7017897 7017897 NS Stainless Steel Check Retainer 7018408 7018408 7018408 ITEM DESCRIPTION ORDERING ORDERING ORDERING NO CODE 6 150MM CODE 8 200MM CODE 10 250MM 1 First Check Module EPDM 7018115 1 First Check Module Red Silicone 7018761 7018118 7018401 2 Second Check Module a EPDM 7018121 2 Second Check Module a Red Silicone 7018765 7...

Страница 7: ...ir or replace hose Relief Valve Replacement Parts Listing ITEM DESCRIPTION ORDERING NO CODE 1 Relief Valve Assembly 7018107 2 Diaphragm RV 7017809 3 Spring RV 7013368 4 Spider Bushing RV 7017811 5 Piston Assembly RV 7018227 6 Body RV 7018889 7 Hose Cover Plate Assembly 7018228 8 Screw Cover RV 7017822 9 O ring Inlet coupler 7017826 10 E Clip 5 per pack 7017870 NS Sensing Elbow 7018888 ITEM DESCRIP...

Страница 8: ...rks 2009 www amesfirewater com A Division of Watts Water Technologies Inc USA Backflow 1427 N Market Blvd Suite 9 Sacramento CA 95834 T 916 928 0123 F 916 928 9333 Control Valves 18550 Hansen Road Houston TX 77075 T 713 943 0688 F 713 944 9445 Canada 5435 North Service Rd Burlington ONT L7L 5H7 T 905 332 4090 F 905 332 7068 ...

Отзывы: