Connection Pipe Requirement
Model
Connecting Pipe inch(mm)
Max. Pipe
Length ft (m)
Max height
difference
between indoor
unit and outdoor
unit ft (m)
Max height difference
between the lowest
and highest indoor
unit ft (m)
Liquid
Gas
M4THM1518A
1/4" (Ø 6)x2
3/8" (Ø 9)x2
75 (22.5)
20 (6)
20 (6)
M4THM1524A
1/4" (Ø 6)x3
3/8" (Ø 9)x3
230 (70)
35 (10)
25 (7.5)
M4THM1530A
1/4" (Ø 6)x4
3/8" (Ø 9)x4
35 (10)
M4THM1536A
1/4" (Ø 6)x3
3/8" (Ø 9.5)x1
3/8" (Ø 9.5)x2
1/2" (Ø 12)x1
5/8" (Ø 16)x1
50 (15)
M4THM1542A
1/4" (Ø 6)x4
3/8" (Ø 9.5)x1
3/8" (Ø 9.5)x2
1/2" (Ø 12)x2
5/8" (Ø 16)x1
260 (79)
50 (15)
NOTES:
1. The connection pipes should be insulated with proper water-proof insulating material
2. Wall thickness of pipe 0.02-0.04 in (0.5-1.0 mm): bearing pressure 435 PSI (3.0 MPa).
3. Shorter connecting pipe lengths result in greater thermal efficiency, so it is preferable to reduce
connecting pipe lengths where possible.
4. Refer to the oil trap instructions for specific requirements when there is height difference
between the indoor and outdoor unit greater than 20 ft. (6m).
NOTICE
The maximum distance of the connection piping in both height and total length is provided in the
table below. Do not install these units in locations that exceed these specifications.