Ameristar M4HP40 Series Скачать руководство пользователя страница 15

15 

NOTE

NOTE

1/2” nut 

5/16” nuts 

Fig.10 COVER AND FAN 

6.3 REMOVING THE TOP PANEL AND MOTOR 

When motor requires changing follow the steps below: 
Step 1: Go into electrical panel, disconnect motor power lines. 

            IMPORTANT NOTE

     

            Disconnect main power to unit. Severe burns and electrical shock will occur if 
            you do not disconnect main power. 
Step 2: Remove cover (be careful of motor wires) 
Step 3: Be sure to place fan cover unit on the ground as indicated in Fig. 10 

            IMPROTANT NOTE

  

            Do not place or lean fan blades on ground or against surface. 
Step 4: Remove fan motor by removing 5/16” nuts from cover. 
Step 5: Remove fan blade from motor by removing 1/2” nut and place fan on the ground. 
Step 6: Reverse removal process to reinstall the fan and motor. 

            IMPROTANT NOTE   

            When connecting motor wires be sure to check motor direction. 

Damage will occur to condenser unit  
if you remove fan nuts prior to cover removal. 

NOTE: 

 

7.0 SYSTEM OPERATION 

7.1 COMPRESSOR CRANKCASE HEATER (CCH) (Heat pump only,

optional

Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase 
heater to minimize refrigeration migration, and to help eliminate any start up noise or 
bearing “wash out”. 
All heaters must be located on the lower half of the compressor shell. Its purpose is to 
drive refrigerant from the compressor shell during long off cycles, thus preventing 
damage to the compressor during start-up. 

The crankcase heating start condition: 

1.The crankcase heating start must meet two conditions:
      A. Outdoor temperature 

37.4° F.

      B. Compressor stops working more than 3 hours.
2. Outdoor temperature 

37.4° F and just connected to the power source.

The crankcase heating stop must meet condition:

Outdoor temperature 

44.6° F or compressor start.

7.2 REVERSING VALVE  INTRODUCTION  (Heat pump only)

Reversing valve

 

energizes at the heating conditions, and cut off at the cooling condition.

At initial start-up or after extended shutdown periods, make sure the heater is energized 
for at least 12 hours before the compressor is started. (Disconnect switch on and wall 
thermostat off.) 

NOTE:

14 SEER

RE

D

 

YE

LLO

W

 

GR

EE

N

 

INDOOR UNIT 

OUTDOOR UNIT 

B

LA

C

K

 

B

LA

C

GROUND 

PLUG PLA TE 

Содержание M4HP40 Series

Страница 1: ...may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death RECOGNIZE THIS SYMBOL AS AN INDICATION OF IM...

Страница 2: ...D LINES 12 4 2 MAXIMUM LENGTH OF LINES 12 4 3 VERTICAL LIFT 12 5 0 EVACUATION 12 6 0 ELECTRICAL CONNECTIONS 14 6 1 GENERAL INFORMATION GROUNDING 14 6 2 FIELD CONNECTIONS POWER WIRING 14 6 3 REMOVING T...

Страница 3: ...alla tion All phases of this installation must comply with NATIONAL STATE AND LOCAL CODES If additional information is required please contact your local distribu tor 3 WARNING Improper installation m...

Страница 4: ...feet Just for scroll compressor 1 2 LIMITATIONS The unit should be installed in accordance with all National State and Local Safety Codes and the limitations listed below As soon as a unit is received...

Страница 5: ...24 15 16 633 24 15 16 633 18 24 HP 30 FIG 2 DIMENSIONS 36 48 60 24 18 AC 30 42 33 3 16 843 3 8 3 4 SUCTION LINE CONNECTION CONTROL WIRING 7 8 22 2mm KNOCKOUT 1 11 32 34 5mm LIQUID LINE CONNECTION SER...

Страница 6: ...the expected snow accumulation in your area Isolate the unit from rain gutters to avoid any possible wash out of the foundation When installing units on a roof the structure must be capable of support...

Страница 7: ...the outdoor unit to facilitate proper oil return 7 3 5 UNIT MOUNTING 2 If elevating a unit on a flat roof use 4 4 or equivalent stringers positioned to distribute unit weight evenly and prevent noise...

Страница 8: ...Prior to installing clear pad of debris IMPORTANT The pad must meet local codes and must be the proper thickness to accommodate fasteners Step 2 Center and level unit onto pad IMPORTANT NOTE These in...

Страница 9: ...se transmis sion from the equipment to the structure 4 The suction line must be insulated Tape and suspend the refrigerant lines as shown DO NOT allow tube metal to metal contact See Fig 5 5 Use PVC p...

Страница 10: ...of the copper unless an inert atmosphere is provide The flow of dry nitrogen should continue until the joint has cooled Always use a pressure regulator and safety valve to insure that only low pressu...

Страница 11: ...ze the suction line to the evaporator suction connection Refer to the Table 1 for proper suction line sizing 6 Protect the suction valve with a wet rag and braze the suction line connection to the out...

Страница 12: ...ation that the system is leak free but still contains moisture and may require further evacuation if the reading is above 350 microns 5 0 EVACUATION 4 0 INTERCONNECTING TUBING 4 1 SUCTION AND LIQUID L...

Страница 13: ...ill result in poor oil return and is not recommended 25 50 100 Optional 0 90 0 90 0 90 0 90 0 91 0 92 0 97 Standard 0 92 0 92 0 93 0 96 0 96 0 96 0 90 150 LINE SIZING 25 50 75 100 125 150 5 16 25 50 6...

Страница 14: ...service access panel and this instruction 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the side of the corner panel Slide corn...

Страница 15: ...ESSOR CRANKCASE HEATER CCH Heat pump only optional Refrigerant migration during the off cycle can result in a noisy start up Add a crankcase heater to minimize refrigeration migration and to help elim...

Страница 16: ...will be OFF T3 143 6 F compressor stop working T3 125 6 F compressor start working When T4 5 F compressor will stop If the electrical heater kit is installed in the indoor unit the outdoor unit would...

Страница 17: ...E if falls between rows or columns then estimate the TARGET LIQUID PRESSURE or SUCTION LINE PRESSURE falls between rows or columns then estimate the TARGET LIQUID PRESSURE between the rows and columns...

Страница 18: ...is permanently lubricated and does not require periodic oiling 3 Refer to the furnace or air handler instructions for filter and blower motor maintenance 4 The indoor coil and drain pan should be ins...

Страница 19: ...ANGE BROWN GREEN BLACK BLACK BLACK GREEN A2 A1 BLACK YELLOW C Y LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED OPTIONAL LOW FACTORY VOLTAGE FACTORY STANDARD FIELD INSTALLED FACTORY OPTIONAL USE COPPER...

Страница 20: ...WIRING TO CONFORM TO I E C N E C C E C C L C AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME GAUGE AND INSULATION TYPE AS ORIGINAL WIRE CC COMPRESSOR CONTACTOR CCH COMP T4 T3 HPC HIGHT...

Страница 21: ...AAA 069 MAYTXVACHP1830AA 14 YES M4CXC030BB1CAAA 070 MAYTXVACHP1830AA 14 YES M4CXC036BC1CAAA 071 MAYTXVACHP1830AA 14 YES M4AH4036A1000AA 071 MAYTXVACHP1830AA 14 YES M4CXC048AB1CAAA 077 MAYTXVACHP3642AA...

Страница 22: ...0 259 279 298 320 341 363 389 415 441 467 204 221 238 257 277 296 318 339 361 387 413 439 465 202 219 236 255 275 294 316 337 359 385 411 437 463 200 217 234 253 273 292 314 335 357 383 409 435 461 19...

Страница 23: ...9 435 460 485 244 265 286 306 327 345 364 382 407 433 458 483 242 263 284 304 325 343 362 380 405 431 456 481 240 261 282 302 323 341 360 378 403 429 454 479 218 238 259 280 300 321 339 358 376 401 42...

Страница 24: ...9 403 427 461 133 213 228 243 257 276 295 314 328 352 376 400 425 459 129 203 220 237 254 273 293 313 327 351 376 398 421 454 125 202 218 234 250 271 291 312 326 350 374 397 420 452 121 201 217 232 24...

Страница 25: ...R F E D T S O R T N O C L O F E D C H C H C H C H C H C H C H C H C H C H C H C H C H C H C H P P P P P P P P P P P P S S S S S S S P P P P S S S S P P P S S P P P P P P P P S S S S S S P P P P P P P...

Страница 26: ...arranty terms shall apply ELIGIBILITY REQUIREMENTS The following items are required in order for the Products to be covered under this limited warranty The Products must be in the same location where...

Страница 27: ...nstalled in M4A3 4 AIR HANDLERS MAYHTR1A Registered Limited Warranty Period Parts ten 10 years SINGLE PHASE R410 OUTDOOR UNITS M4AC3 M4AC3018 24 30 36 42 48 60 only M4HP3 M4AC4 M4HP4 Registered Limite...

Страница 28: ...2020001C0543 V1 0 TR MD14U 035AW...

Отзывы: