NOTE
NOTE
1/2” nut
5/16” nuts
Fig.10 COVER AND FAN
6.3 REMOVING THE TOP PANEL AND MOTOR
When motor requires changing follow the steps below:
Step 1: Go into electrical panel, disconnect motor power lines.
IMPORTANT NOTE
Disconnect main power to unit. Severe burns and electrical shock will occur if
you do not disconnect main power.
Step 2: Remove cover (be careful of motor wires)
Step 3: Be sure to place fan cover unit on the ground as indicated in Fig. 10
IMPROTANT NOTE
Do not place or lean fan blades on ground or against surface.
Step 4: Remove fan motor by removing 5/16” nuts from cover.
Step 5: Remove fan blade from motor by removing 1/2” nut and place fan on the ground.
Step 6: Reverse removal process to reinstall the fan and motor.
IMPROTANT NOTE
When connecting motor wires be sure to check motor direction.
Damage will occur to condenser unit
if you remove fan nuts prior to cover removal.
NOTE:
7.0 SYSTEM OPERATION
7.1 COMPRESSOR CRANKCASE HEATER (CCH) (Heat pump only,
optional
)
Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase
heater to minimize refrigeration migration, and to help eliminate any start up noise or
bearing “wash out”.
All heaters must be located on the lower half of the compressor shell. Its purpose is to
drive refrigerant from the compressor shell during long off cycles, thus preventing
damage to the compressor during start-up.
The crankcase heating start condition:
1.The crankcase heating start must meet two conditions:
A. Outdoor temperature
<
37.4° F.
B. Compressor stops working more than 3 hours.
2. Outdoor temperature
<
37.4° F and just connected to the power source.
The crankcase heating stop must meet condition:
Outdoor temperature
>
44.6° F or compressor start.
7.2 REVERSING VALVE INTRODUCTION (Heat pump only)
Reversing valve
energizes at the heating conditions, and cut off at the cooling condition.
At initial start-up or after extended shutdown periods, make sure the heater is energized
for at least 12 hours before the compressor is started. (Disconnect switch on and wall
thermostat off.)
NOTE:
14 SEER
C
RE
D
YE
LLO
W
GR
EE
N
Y
R
G
INDOOR UNIT
OUTDOOR UNIT
G
C
Y
B
LA
C
K
R
C
B
LA
C
K
GROUND
PLUG PLA TE