Operating the Temperature Control System
Figure 24: Status Codes
ON
OFF
STATUS
A
B C
•
•
VE
RY
HOT
HOT
LOW
VAC
Status
Light
Water Temperature Adjustment
The water temperature can be adjusted from 70°F to 160°F.
Turn the Gas Control/Temperature Knob to the desired
setting/temperature.
Operating Modes and Settings
•
Standard Mode
- The controller adjusts the water
heater to maintain the temperature set by the user.
• Vacation
Setting
- The controller adjusts the water
temperature to approximately 70°F. This setting is
recommended when the water heater is not in use for
a long period of time. This effectively turns the water
heater down to a setting that prevents the water from
freezing.
Status Light Code
Table 6
LED FLASH SEQUENCE
CONTROL STATUS
Short flash once every four second
IDLE (No call for heat, no fault conditions)
“Heartbeat”, alternates bright/dim
Call for Heat (No fault conditions)
One Flash, three second pause
Low Flame Signal (control continues to operate)
Two Flash, three second pause
End Switch Failed Closed
Three Flash, three second pause
End Switch Failed Open or TCO Limit Lockout
Four Flash, three second pause
ECO Limit Lockout
Five Flash, three second pause
Flame Out of Sequence
Six-One Flash, three second pause
Soft Lockout - Retry Limit - Failed TFI
Six-Two Flash, three second pause
Soft Lockout - Recycle Limit - Flame Lost - END Switch Fails
Six-Three Flash, three second pause
Soft Lockout - Recycle Limit - Flame Lost
Six-Four Flash, three second pause
Soft Lockout - Flame out of Sequence Sensed
Seven Flash, three second pause
Flammable Vapor Sensor (FVS) Lockout
Eight-One Flash, three second pause
Flammable Vapor Sensor (FVS) Fault Detected
Eight-Two Flash, three second pause
Temperature Sensor Fault Detected
Eight-Three Flash, three second pause
Electronic Fault Detected
Eight-Four Flash, three second pause
Gas Control Valve/Thermostat Fault Detected