© American Time
12
SQA461RSxE Owner's Manual
A
pp
e
nd
ix
M
ai
n
te
n
a
n
ce
Co
de
B
lue
O
p
e
rat
io
n
In
st
a
ll
at
io
n
D
e
scr
ip
ti
o
n
Code Blue
Description
The Code Blue feature provides an override which forces the clock into a special count up elapsed time mode. No matter
which of the three normal functions is being displayed, Code Blue input will cause the unit to begin counting elapsed time
from 00:00:00. All other functions of the unit continue to operate in the background during a Code Blue.
Operation
A Code Blue is initiated by applying a signal ranging from 12vac/vdc to 30vac/vdc to the K2+ and K2- terminals. See the
sample wiring diagram below for more detail.
The Code Blue timer is the highest priority function of the clock/timer while in the run mode. No matter which of the 3 normal
functions is being displayed, the Code Blue input will cause the clock to begin counting up elapsed time from 00:00:00.
The Code Blue timer can be stopped and the time held for viewing by pressing the START/STOP button on the ATSTCS switch
panel. The Code Blue timer cannot be restarted from the switch panel.
To reset the clock back to normal operation, the RUN/SET switch must be set to the SET position momentarily and then
returned to the RUN position.
All other functions of the clock continue to operate in the background during a Code Blue. Time of day and time corrections
from the SiteSync IQ system controller will not be affected. The standard count up timer and the count down timer will
continue as well. However, if one of these timers is switched on for display when a Code Blue occurs, that particular timer
will be reset when the clock is reset back to normal operation.
K2+
K2–
K1+
K1–
12V
AC
12V
AC
UNREG
GND
PIEZ
O
S5
S4
S3
S2
S1
NO
T USED
NO
T USED
RED
BLA
CK
VIOLE
T
GRE
Y
BR
OWN
BL
UE
OR
ANGE
YELL
OW
GREEN
WHITE
PIEZO
BUZZER
RESET
ENTER
START/STOP
INCREMENT
UP
CL
OCK
DOWN
SET
RUN
Green-Earth Gnd
White-Neutral line
Black-Hot line
Digital Clock/Timer
ATSTCS Control Station
20 ft. supplied cable. Can
be extended to 30 ft.
maximum using #22 AWG
wire (min.) with 1/32”
insulation (min.)
Digital Clock/Timer Code Blue wiring using Control Station
The Control Station is connected as normal.