Control Station Installation
The ATSTCS Control Station can be mounted to a double gang box, 1
1
/
2
inch deep or deeper. The Control Station can be
mounted up to 30 feet away from the Digital Clock/Timer. The recommended minimum interconnecting field wire size is
#22.8 AWG stranded wire.
Ensure that
installation conforms to the National Electrical Code and local wiring codes.
CAUTION: Electric Shock Hazard!
Ensure that no electrical power is present on any wire before installation.
u
Pull interconnecting field wires into the double gang box.
v
Connect field wiring interconnecting the ATSTCS Control Station with the Digital Clock/Timer to the
appropriate wires of the Control Station. See wiring detail below.
w
Mount the Control Station to the double gang box using the machine screws provided.
K2+
K2–
K1+
K1–
12V
AC
12V
AC
UNREG
GND
PIEZ
O
S5
S4
S3
S2
S1
NO
T USED
NO
T USED
RED
BLA
CK
VIOLE
T
GRE
Y
BR
OWN
BL
UE
OR
ANGE
YELL
OW
GREEN
WHITE
PIEZO
BUZZER
RESET
ENTER
START/STOP
INCREMENT
UP
CL
OCK
DOWN
SET
RUN
Green-Earth Gnd
Red-Optional
correction line
White-Neutral line
Black-Hot line
Digital Clock/Timer
ATSTCS Control Station
20 ft. supplied cable. Can
be extended to 30 ft.
maximum using #22 AWG
wire (min.) with 1/32”
insulation (min.)
Typical wiring for the Digital Clock/Timer with Control Station