INSTALLATION

IMPORTANT: Do not lift the unit without test lifting for
balance and rigging.  Do not lift the unit in windy conditions
or above personnel.  Do not lift the unit by attaching a
clevis, hooks, pins, or bolts to the unit casing, casing
hardware, corner lugs, angles, tabs, or flanges.  Failure to
observe these warnings may result in equipment damage.

4. When the curb and air ducts have been properly installed, the

unit is ready to be hoisted to the roof and set in position.

IMPORTANT:  “Spreader Bars” must be used when hoist-
ing the unit.

5. IMPORTANT:   The unit must be lowered into position.  The

P.V.C. rubber tape on the curb flange permits the unit to be
repositioned if required without destroying the P.V.C. rub-
ber seals affixed to the mounting curb.

PLACING THE UNIT ON A MOUNTING CURB

1. The unit is designed with a perimeter drip lip that is lower that

the unit base bar, see Figure 7, inset A.

2. Position the unit drip lip down over and in contact with the

outside corner of the curb, as illustrated in Figure 8, insert A.
Continue to lower the unit on top of the curb, with the unit drip
lip astraddle and in contact with both the end and side rail of the
curb. The unit should now rest on top of the curb.

3. Take the two (2) hold-down brackets shipped with the curb and

secure the unit to the curb with hold-down brackets as illus-
trated in Figure 8, insert A.

 

7

 

8

SPREADER BARS

OUTDOOR COIL

END OF UNIT

GASKET SEAL

BASE OF UNIT

REST ON TOP OF

CURB RAILS

DRIP LIP

DIMPLE

BAYLIFT002A

LIFTING LUGS

SEE DETAIL “A”

“B”

“A”

DRIP LIP ON

PERIMETER OF UNIT

UNIT CORNER

CURB CORNER

EXISTING

SHEET METAL

SCREW

HOLD-DOWN

BRACKET WITH

CURB

FLANGE OF

CURB

“A”

NOTE:

THE INNER PERIMETER OF THE DRIP LIP ON ALL UNITS
SHOULD BE FLUSH WITH THE OUTER PERIMETER OF THE
CURB ON THE TWO SIDES SHOWN HERE. SEE FIGURE 2 FOR
THE LOCATION OF THE UNIT OVERHANG ON THE
YCX024-060G MODELS.

Содержание YCP-IOM-1C

Страница 1: ...h NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Single Package Gas Elect...

Страница 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Страница 3: ...F H YCP042F M YCP048F H YCP060F M TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS YCP024 036F L M Models on BAYCURB030 38A 1 2 ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY A...

Страница 4: ...6 1 2 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 21 21 7 8 YCP030F L 84 68 93 111 356 YCP030F M 85 70 94 114 363 YCP036F L 88 73 97 114 372 20 1 2 25 1 8 YCP036F M 88 74 97 119 379 YCP036F H 93 76 1...

Страница 5: ...30F L YCP030F M YCP036F L YCP036F M YCP036F H 64 36 29 3 16 26 9 16 YCP042F M YCP048F H 65 1 8 45 33 5 8 27 15 16 YCP060F M RECOMMENDED SERVICE CLEARANCE BACK 6 0 LEFT SIDE 30 0 RIGHT SIDE 24 0 FRONT...

Страница 6: ...S SERVICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT R...

Страница 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Страница 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Страница 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Страница 10: ...OP APPLICATION WITH FRAME YCP024 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Страница 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Страница 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Страница 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Страница 14: ...3 8 inches water column 5 Using an appropriate backup wrench on the gas valve inlet boss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the...

Страница 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Страница 16: ...xible conduit supports whenever vibration transmission may cause a noise problem within the building structure Be sure all connections are made tight See Figure 18 NOTES For branch circuit wiring main...

Страница 17: ...e leaving the unit or turning on the power to the unit ELECTRICAL WIRING YCP F FIELD WIRING DIAGRAM i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Страница 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Страница 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Страница 20: ...d the gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the val...

Страница 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Страница 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Страница 23: ...ce labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by u...

Страница 24: ...warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for the...

Отзывы: